Star Connection in a 3 Phase System

Edwiin
05/27/2025

Star Connection in Three-Phase Systems
In a star (Y) connection, the similar ends (either starts or finishes) of the three windings are joined at a common point called the star or neutral point. The three line conductors extend from the remaining free terminals to form the phase connections.
For a three-phase, three-wire system, only the three line conductors are connected to the external circuit. Alternatively, a four-wire system includes a neutral conductor drawn from the star point, as illustrated in the diagram below:
Star Connection Analysis with Phase and Line Quantities
With reference to the figure above, the finish terminals (a2, b2, c2) of the three windings are joined to form the star (neutral) point. The three line conductors (labeled R, Y, B) extend from the remaining free terminals, as illustrated.
  • Phase current (Iₚₕ): Current through each winding phase.
  • Line current (Iₗ): Current through each line conductor.
  • Phase voltage (Eₚₕ): Voltage across each winding phase.
  • Line voltage (Eₗ): Voltage between two line conductors.
Phase Voltage vs. Line Voltage in Star Connection
The star connection configuration is depicted in the figure below:
Star Connection in Balanced Three-Phase Systems
In a balanced system, the three phases (R, Y, B) carry equal currents. Consequently, the phase voltages ENR, ENY, and ENB are equal in magnitude but displaced by 120° electrical from each other.
Phasor Diagram of Star Connection
The phasor diagram for the star connection is shown below:

The arrowheads on the EMFs and current indicate direction and not their actual direction at any instant.

Now,

Hence, in star connection line voltage is root 3 times of phase voltage.

Hence, in a 3 Phase system of star connections, the line current is equal to phase current.

Edwiin

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

Working Voltage in Power System
Working Voltage in Power System
Working VoltageThe term "working voltage" refers to the maximum voltage that a device can withstand without sustaining damage or burning out, while ensuring the reliability, safety, and proper operation of both the device and associated circuits.For long-distance power transmission, the use of high voltage is advantageous. In AC systems, maintaining a load power factor as close to unity as possible is also economically necessary. Practically, heavy currents are more challenging to handle than hi
Encyclopedia
07/26/2025
Frequency division method for measuring grid-to-ground insulation parameters
Frequency division method for measuring grid-to-ground insulation parameters
The frequency division method enables the measurement of grid-to-ground parameters by injecting a current signal of a different frequency into the open delta side of the potential transformer (PT).This method is applicable to ungrounded systems; however, when measuring the grid-to-ground parameters of a system where the neutral point is grounded via an arc suppression coil, the arc suppression coil must be disconnected from operation beforehand. Its measurement principle is shown in Figure 1.As
Leon
07/25/2025
The insulation parameters of the power grid to ground are measured by the tuning method
The insulation parameters of the power grid to ground are measured by the tuning method
The tuning method is suitable for measuring the ground parameters of systems where the neutral point is grounded via an arc suppression coil, but not applicable to ungrounded neutral point systems. Its measurement principle involves injecting a current signal with continuously varying frequency from the secondary side of the Potential Transformer (PT), measuring the returned voltage signal, and identifying the system's resonant frequency.During the frequency sweeping process, each injected heter
Leon
07/25/2025
Effect of Transition Resistance at the Grounding Point on the Rising Speed of Zero - sequence Voltage
Effect of Transition Resistance at the Grounding Point on the Rising Speed of Zero - sequence Voltage
In an arc - suppression coil grounding system, the rising speed of the zero - sequence voltage is greatly affected by the value of the transition resistance at the grounding point. The larger the transition resistance at the grounding point, the slower the rising speed of the zero - sequence voltage.In an ungrounded system, the transition resistance at the grounding point has basically no impact on the rising speed of the zero - sequence voltage.Simulation Analysis: Arc - suppression Coil Ground
Leon
07/24/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!