• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


How to Handle Overheating of Busbar Isolating Switches

Felix Spark
Field: Failure and maintenance
China

Overheating of Busbar Isolating Switches: Causes and Handling Procedures

Overheating of busbar isolating switches is a common electrical equipment defect. If not addressed promptly, the situation can severely deteriorate during a system short circuit—when high short-circuit current flows through the overheated point, potentially causing contact melting or even destruction of the switch.

Isolating Switch..jpg

When overheating of a busbar isolating switch is detected, follow these steps for safe handling:

  • Report the defect to the grid dispatcher and request load reduction to lower the current through the affected circuit.

  • If a bypass busbar is available, use the bypass circuit breaker to take over the load, allowing the overheated busbar isolating switch to be taken out of service.

  • If conditions permit, energize a standby line, open the circuit breaker of the faulty line, and then open the overheated busbar isolating switch for maintenance.

  • If neither bypass operation nor de-energization is possible, apply the following measures based on the busbar configuration:

    • For single-busbar configurations:
      Minimize the load current in the affected circuit as much as possible. Improve cooling conditions (e.g., by installing temporary forced ventilation fans), enhance real-time monitoring, and coordinate with the dispatcher to create conditions for an early outage and repair.

    • For double-busbar configurations:
      Reconfigure the system operation mode—close the spare busbar isolating switch and open the faulty (overheated) one to isolate it from service. Ensure that bus differential protection and non-selective switching logic remain correctly configured and functional during the transition.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
01/29/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.