Overheating of Busbar Isolating Switches: Causes and Handling Procedures

Overheating of busbar isolating switches is a common electrical equipment defect. If not addressed promptly, the situation can severely deteriorate during a system short circuit—when high short-circuit current flows through the overheated point, potentially causing contact melting or even destruction of the switch.

Isolating Switch..jpg

When overheating of a busbar isolating switch is detected, follow these steps for safe handling:

  • Report the defect to the grid dispatcher and request load reduction to lower the current through the affected circuit.

  • If a bypass busbar is available, use the bypass circuit breaker to take over the load, allowing the overheated busbar isolating switch to be taken out of service.

  • If conditions permit, energize a standby line, open the circuit breaker of the faulty line, and then open the overheated busbar isolating switch for maintenance.

  • If neither bypass operation nor de-energization is possible, apply the following measures based on the busbar configuration:

    • For single-busbar configurations:
      Minimize the load current in the affected circuit as much as possible. Improve cooling conditions (e.g., by installing temporary forced ventilation fans), enhance real-time monitoring, and coordinate with the dispatcher to create conditions for an early outage and repair.

    • For double-busbar configurations:
      Reconfigure the system operation mode—close the spare busbar isolating switch and open the faulty (overheated) one to isolate it from service. Ensure that bus differential protection and non-selective switching logic remain correctly configured and functional during the transition.

Give a tip and encourage the author!
Recommended
Manual or Electric Isolator Not Opening? Here’s What to Do
Manual or Electric Isolator Not Opening? Here’s What to Do
Isolating Switch: Definition and OverviewAn isolating switch (or disconnector) is a switching device primarily used for isolating power sources, switching operations (bus transfer), and making or breaking small-current circuits. It has no arc-quenching capability.When in the open position, there is a specified insulation distance between contacts and a clearly visible disconnection indicator. When in the closed position, it can carry the normal operating current and, for a specified duration, th
Garca
11/08/2025
Why Capacitor Bank Isolators Overheat & How to Fix
Why Capacitor Bank Isolators Overheat & How to Fix
Causes of High Temperature in Isolating Switches of Capacitor Banks and Corresponding SolutionsI. Causes: OverloadThe capacitor bank is operating beyond its designed rated capacity. Poor ContactOxidation, loosening, or wear at contact points increases contact resistance. High Ambient TemperatureElevated external environmental temperatures impair the switch’s ability to dissipate heat. Inadequate Heat DissipationPoor ventilation or dust accumulation on heat sinks hinders effective cooling. Harmon
Felix Spark
11/08/2025
Analysis of Isolating Switch Applications in Generator Neutral Grounding Resistor Cabinets
Analysis of Isolating Switch Applications in Generator Neutral Grounding Resistor Cabinets
Application of Isolating Switches in Generator Neutral Grounding Resistor CabinetsIsolating switches are commonly installed in NS-FZ generator neutral grounding resistor cabinets. They provide a clearly visible disconnection point, ensuring the safety of maintenance and testing personnel. However, as high-voltage devices without arc-quenching capability, isolating switches must only be operated when the circuit is de-energized—i.e., under no-load conditions.The primary function of an isolating s
Echo
11/08/2025
Centralized vs Distributed Solar Power: Key Differences
Centralized vs Distributed Solar Power: Key Differences
Differences Between Centralized and Distributed Photovoltaic (PV) Power PlantsA distributed photovoltaic (PV) power plant refers to a power generation system that consists of multiple small-scale PV installations deployed across various locations. Compared to traditional large-scale centralized PV power plants, distributed PV systems offer the following advantages: Flexible Layout: Distributed PV systems can be flexibly installed based on local geographic conditions and electricity demand—in div
Echo
11/08/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.