• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What are Faults in Transformer?

Encyclopedia
Field: Encyclopedia
0
China


What are Faults in Transformer?


Definition of Transformer Faults


Faults in transformer refer to issues like insulation breakdowns and core faults that can occur inside or outside the transformer.

 


External Faults in Power Transformer

 


External Short Circuit of Power Transformer


 

Short circuits can happen in two or three phases of the electrical power system. The fault current is usually high, depending on the short-circuited voltage and circuit impedance up to the fault point. This high fault current increases copper loss, causing internal heating in the transformer. It also creates severe mechanical stresses, especially during the first cycle of the fault current.


High Voltage Disturbance in Power Transformer


 

High voltage disturbance in power transformer are of two kinds,



  • Transient Surge Voltage

  • Power Frequency Over Voltage

 


Transient Surge Voltage


High voltage and high frequency surge may arise in the power system due to any of the following causes,

 


  • Arcing ground if neutral point is isolated.

  • Switching operation of different electrical equipment.

  • Atmospheric Lightening Impulse.

 


Whatever may be the causes of surge voltage, it is after all a traveling wave having high and steep wave form and also having high frequency. This wave travels in the electrical power system network, upon reaching in the power transformer, it causes breakdown of the insulation between turns adjacent to line terminal, which may create short circuit between turns.


Power Frequency Over Voltage


There may be always a chance of system over voltage due to sudden disconnection of large load. Although the amplitude of this voltage is higher than its normal level but frequency is same as it was in normal condition. Over voltage in the system causes an increase in stress on the insulation of transformer. As we know that, voltage , increased voltage causes proportionate increase in the working flux.

 

2f0db1edff2b8e96f0313ed94c801420.jpeg

 

This therefore causes, increased in iron loss and proportionately large increase in magnetizing current. The increase flux is diverted from the transformer core to other steel structural parts of the transformer. Core bolts which normally carry little flux, may be subjected to a large component of flux diverted from saturated region of the core alongside. Under such condition, the bolt may be rapidly heated up and destroys their own insulation as well as winding insulation.

 


Under Frequency Effect in Power Transformer


As, voltage as the number of turns in the winding is fixed.From, this equation it is clear that if frequency reduces in a system, the flux in the core increases, the effect are more or less similar to that of the over voltage.

 

c5e82df6f5477f495e2253467fcd55f8.jpeg

 

Internal Faults in Power Transformer


The principle faults which occurs inside a power transformer are categorized as,

 


  • Insulation breakdown between winding and earth

  • Insulation breakdown in between different phases

  • Insulation breakdown in between adjacent turns i.e. inter – turn fault

  • Transformer core fault

 


Internal Earth Faults in Power Transformer


Internal Earth Faults in a Star Connected Winding with Neutral Point Earthed through an Impedance


In a star-connected winding with the neutral point earthed through an impedance, fault current depends on the earthing impedance and the distance from the fault point to the neutral. The voltage at the fault point is higher if it is further from the neutral, leading to higher fault current. Fault current also depends on the leakage reactance of the winding portion across the fault point and neutral, but this is usually low compared to earthing impedance.


Internal Earth Faults in a Star Connected Winding with Neutral Point Solidly Earthed

 


In this case, earthing impedance is ideally zero. The fault current is dependent up on leakage reactance of the portion of winding comes across faulty point and neutral point of transformer. The fault current is also dependent on the distance between neutral point and fault point in the transformer.


As said in previous case the voltage across these two points depends upon the number of winding turn comes across faulty point and neutral point. So in star connected winding with neutral point solidly earthed, the fault current depends upon two main factors, first the leakage reactance of the winding comes across faulty point and neutral point and secondly the distance between faulty point and neutral point. 


But the leakage reactance of the winding varies in complex manner with position of the fault in the winding. It is seen that the reactance decreases very rapidly for fault point approaching the neutral and hence the fault current is highest for the fault near the neutral end. So at this point, the voltage available for fault current is low and at the same time the reactance opposes the fault current is also low, hence the value of fault current is high enough. 


Again at fault point away from the neutral point, the voltage available for fault current is high but at the same time reactance offered by the winding portion between fault point and neutral point is high. It can be noticed that the fault current stays a very high level throughout the winding. In other word, the fault current maintain a very high magnitude irrelevant to the position of the fault on winding.


Internal Phase to Phase Faults in Power Transformer


Phase to phase fault in the transformer are rare. If such a fault does occur, it will give rise to substantial current to operate instantaneous over current relay on the primary side as well as the differential relay.


Inter Turns Fault in Power Transformer


Power transformer connected with electrical extra high voltage transmission system, is very likely to be subjected to high magnitude, steep fronted and high frequency impulse voltage due to lightening surge on the transmission line. The voltage stresses between winding turns become so large, it can not sustain the stress and causing insulation failure between inter – turns in some points. Also LV winding is stressed because of the transferred surge voltage. Very large number of power transformer failure arises from fault between turns. Inter turn fault may also be occurred due to mechanical forces between turns originated by external short circuit.


Core Fault in Power Transformer


If any part of the core lamination is damaged or bridged by a conducting material, it can cause eddy current and local overheating. This can also happen if the insulation of bolts used to tighten the core laminations fails. These faults cause severe local heating but don’t significantly affect the transformer input and output current, making them hard to detect with standard electrical protection schemes. Excessive overheating can break down transformer oil, releasing gases that accumulate in the Buchholz relay and trigger an alarm. 


Give a tip and encourage the author!

Recommended

Rockwill Powers Cambodia’s Battambang Solar-Storage Project
The Battambang Conch PV + Energy Storage Power Station in Cambodia has successfully completed its grid-connected trial operation. The project utilized medium-voltage switchgear supplied by Rockwill Intelligent Electric Co., Ltd. Despite numerous challenges—including an extremely tight delivery schedule—Rockwill Intelligent delivered high-quality products and exceptional service throughout project execution, earning consistent praise from the client.Located in Battambang, Cambodia, the Battambang
12/24/2025
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.