• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What is the Annealing Test for Wires and Conductors ?

Encyclopedia
Field: Encyclopedia
0
China


What is the Annealing Test for Wires and Conductors ?


Annealing Test Definition


The annealing test is performed to ensure the durability and flexibility of wires and conductors during twisting and bending.


Specimen Preparation


A specific gauge length of the conductor is used for the test, ensuring accurate results.


Testing Equipment


A tensile testing machine, micrometer, and measuring scale are essential for conducting the annealing test.


Elongation Measurement


The test measures the elongation percentage of the specimen after it fractures.


Process of annealing test for wires and conductors


A conductor specimen is selected for testing. It must be of a specified gauge length for accurate results. The total length includes the gauge length and extra lengths at both ends for holding in the tensile test machine.


A tensile testing machine is used, which is automatic and meets the test requirements. The machine must firmly grip the specimen. Additional tools include a plane-faced micrometer with 0.01 mm divisions and a measuring scale with 1 mm divisions. Only one specimen is needed, and no pre-conditioning is required. The specimen is fixed, and tensile stress is applied gradually until it fractures, with an elongation rate not exceeding 100 mm per minute.


The elongation is measured on the gauge length after the fractured ends have been fitted together. The elongation is expressed as a percentage of the original specimen gauge length. Main observation of annealing test for wires and conductors is that whether the specimen meets or does not meet the specified maximum allowed elongation. Plane Faced Micrometer with scale division at least 0.01 mm is used to measure the diameter of the specimen used in the test.

 

339ea88f807e1c6a14c5bbdf5a354a50.jpeg

d4721788fdf37b70235fc196cfbb3248.jpeg 

Calculation

 

3631c6f6e25338e739f558caff5f7572.jpeg

 

Where, L = original gauge length of specimen

and L’ = elongated length of specimen


Result Reporting


The results indicate if the specimen meets the specified elongation requirements.

  

 


Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.