• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Specifications or Rating of Power Capacitor Bank

Encyclopedia
Field: Encyclopedia
0
China

Capacitor Bank Definition


A capacitor bank is defined as a group of capacitors used to store and release electrical energy in a power system, helping to improve power quality.


System Voltage Tolerance


Capacitor banks must operate smoothly at up to 110% of the rated peak phase voltage and 120% of the rated RMS phase voltage.


KVAR Rating


Capacitor unit are normally rated with its KVAR ratings. Standard capacitor unit available at market, are typically rated with either of following KVAR rating.50 KVAR, 100 KVAR, 150 KVAR, 200 KVAR, 300 KVAR and 400 KVAR.The KVAR delivered to the power system depends upon the system voltage by the following formula.

 

66df1878cf1f69b0b6a05bcbe3d85500.jpeg

 

Temperature Rating of a Capacitor Bank


These are mainly two cause of farming heat on a capacitor bank.

 

Outdoor type capacitor bank are generally installed at open space where sunlight strikes on the capacitor unit directly. Capacitor can also absorb heat from the nearly furnace for which it is installed.

Production of heat in the capacitor unit is also initiated from the VAR delivering by the unit.



Hence, for radiation of these heats, there should be sufficient arrangement. The maximum allowable ambient temperatures in which a capacitor bank should be operated are given below in tabular form,


Heat Management


Proper ventilation and spacing are necessary to manage heat from external and internal sources to maintain capacitor bank efficiency.


9de956987363bc28fd88075e7628bcdd.jpeg

 

To ensure proper ventilation, there should be adequate spacing between capacitor units. Sometimes, forced airflow can be used to speed up heat dissipation from the bank.


Capacitor Bank Unit or Capacitor Unit


Capacitor bank units or simply called capacitor units are manufactured in either single phase or three phase configuration.


Single Phase Capacitor Unit


Single phase capacitor units are designed either double bushing or single bushing.


Double Bushing Capacitor Unit


Here, the terminal of the both ends of capacitor assembly are come out from the metallic casing of the unit through two bushing. The entire capacitor assembly, this is series parallel combination of required number of capacitive elements is immersed in insulating fluid casing. Hence, there will be an insulated separation between conducting part of the capacitor element assembly go through bushing, there will be no connection between conductor and casing. That is why double bushing capacitor unit is known as dead tank capacitor unit.


Single Bushing Capacitor Unit


In this case casing of the unit is used as second terminal of assembly of capacitor element. Here single bushing is used to terminal one end of the assembly and its other terminal is internally connected to the metallic casing. This is possible because except terminal, all other conducting portion of the capacitor assembly is insulated from the casing.


Three Bushing Capacitor Unit


A three phase capacitor unit has three bushings to terminate 3 phase respectively. There is no neutral terminal in 3 phase capacitor unit.


BIL or Basic Insulation Level of Capacitor Unit


Like other electrical equipments a capacitor bank has also to with stand different voltage conditions, like power frequency over voltages and lightening and switching over voltages.

So Basic Insulation Level must be specified on every capacitor unit rating plate.

 

Internal Discharge Device


Capacitor units usually have an internal discharge device that quickly reduces residual voltage to a safe level, typically 50 V or less, within a specified time. The discharge period is part of the unit’s rating.

 

Transient Over Current Rating


Power capacitor may undergo over current situating during switching operation. So the capacitor unit must be rated for allowable short circuit current for specified time period.So, a capacitor unit should be rated with all the above mentioned parameters.


So a power capacitor unit can be rated as follows,


  • Nominal system voltage in KV.



  • System power frequency in Hz.



  • Temperature class with allowable maximum and minimum temperature in oC.



  • Rated voltage per unit in KV.



  • Rated output in KVAR.



  • Rated capacitance in µF.



  • Rated current in Amp.



  • Rated insulation level (Nominal voltage/Impulse voltage).



  • Discharge time/voltage in second/voltage.



  • Fusing arrangement either internally fused or externally fused or fuseless.



  • Number of bushing, double/single/triple bushing.


  • Number of phase. Single phase or three phase.



Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.