• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Front-Panel Visible Wiring Standards for Electrical Control Panels

James
Field: Electrical Operations
China

Front-panel visible wiring: During manual wiring (not using templates or molds), wiring must be straight, neat, closely attached to the mounting surface, rationally routed, and with secure connections that facilitate maintenance.

Visible Wiring Standards.jpg

  1. Wiring channels should be minimized as much as possible. Within the same channel, bottom-layer conductors shall be grouped by main and control circuits, arranged in a single-layer parallel dense layout or bundled, and kept closely attached to the mounting surface.

  2. Conductor length should be as short as possible. Horizontal aerial spans are permitted—for example, between two coil terminals or between main contact terminals—provided a certain amount of slack is left, and such conductors need not be tightly attached to the mounting surface.

  3. Conductors on the same plane shall be aligned at the same height or depth and must not cross. If crossing is unavoidable, a horizontal aerial span may be used, but only if it constitutes rational routing.

  4. Wiring must be horizontally level and vertically straight, with direction changes made at 90° angles.

  5. If upper and lower contact points are not vertically aligned, diagonal wiring shall not be used.

  6. When connecting conductors to terminal blocks or studs, the insulation layer must not be pinched, reverse loops are prohibited, and exposed copper shall not exceed 1 mm. Additionally, the spacing between conductors at different connection points of the same component or same circuit shall remain consistent.

  7. No more than two conductors shall be connected to a single terminal of an electrical component. Generally, only one conductor is allowed per terminal segment on a terminal block.

  8. During wiring, the conductor core and insulation must not be damaged.

  9. When conductors of different cross-sectional areas are used, those with larger cross-sections shall be placed in the lower layer, and those with smaller cross-sections in the upper layer.

  10. When routing multiple conductors (main power circuits), they shall be arranged so that the entire group lies on the same horizontal or vertical plane.

  11. Coding sleeves may be omitted if the wiring is simple.

Wire color coding:

  1. Protective earth (PE) conductors must be green-and-yellow.

  2. Neutral (N) and mid-point (M) conductors in power circuits must be light blue.

  3. AC or DC power circuits shall use black conductors.

  4. AC control circuits shall use red conductors.

  5. DC control circuits shall use blue conductors.

  6. Interlock conductors in control circuits that remain live when the external control circuit is disconnected shall be orange or yellow.

  7. Circuits connected to the protective conductor shall use white conductors.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
01/29/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.