• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


How Altitude Affects HV Equipment Insulation & Temperature Rise?

James
Field: Electrical Operations
China

As altitude increases, air density, temperature, and atmospheric pressure decrease accordingly, leading to reduced dielectric strength of air gaps and external insulation performance of porcelain components. This results in degraded external insulation performance for high-voltage electrical equipment. Since most high-voltage equipment is designed for installation at altitudes below 1,000 meters, using such equipment at elevations exceeding 1,000 meters may compromise reliable insulation performance. Therefore, the external insulation strength of high-voltage switchgear used in high-altitude areas must be enhanced.

For high-altitude regions above 1,000 meters (up to 4,000 meters), it is generally required that for every additional 100 meters of elevation, the external insulation test voltage be increased by 1% during equipment selection and testing.

Temperature Rise.jpg

For high-voltage equipment operating at altitudes between 2,000 and 3,000 meters with voltages up to 110kV, the external insulation strength is typically enhanced by selecting equipment with one higher insulation level—this increases the impulse and power-frequency withstand voltages by approximately 30%.

For correction methods and calculations regarding external insulation at high altitudes, refer to IEC 62271-1, GB 11022, and Q/GDW 13001-2014 Technical Specification for External Insulation Configuration in High-Altitude Areas.

In addition to the impact of altitude on external insulation, according to IEC standards, if the temperature rise test of high-voltage equipment is conducted at an altitude below 2,000 meters, the temperature rise performance must be re-evaluated when the equipment is deployed at altitudes between 2,000 and 4,000 meters. This is because thinner air reduces the effectiveness of natural convection cooling.

Under normal test conditions, the measured temperature rise must not exceed the values specified in Table 3 of IEC 62271-1. When equipment is installed at altitudes above 2,000 meters, the allowable maximum temperature limit should be reduced by 1% for every additional 100 meters of elevation. However, in practice, it is generally unnecessary to impose special temperature rise limits based solely on increasing altitude. This is because higher altitudes are associated with lower substation ambient temperatures. Even if the temperature rise is higher, the final operating temperature of the equipment remains within acceptable limits (it is the final temperature, not the temperature rise, that affects equipment performance). Different altitudes correspond to different maximum ambient air temperatures, as shown in the table below.

Table 1: Maximum Ambient Air Temperature Corresponding to Different Altitudes

Altitude / m Maximum Ambient Air Temperature / °C
0~2000 40
2000~3000 35
3000~4000 30

In addition to affecting the external insulation of the primary (high-voltage) parts of high-voltage electrical equipment, high altitude also impacts control devices. Control cabinets may contain secondary components such as motors, circuit breakers, contactors, and relays, most of which rely on air insulation. Therefore, their insulation performance also degrades at high altitudes. This factor must be considered during equipment selection.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
01/29/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.