• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Outdoor Substations: Types, Pros & Cons (55kV–765kV)

Edwiin
Field: Power switch
China

Substations designed for voltage levels ranging from 55 kV to 765 kV are known as outdoor substations. This type of substation requires less construction time but occupies more space. Outdoor substations are mainly divided into pole-mounted substations and foundation-mounted substations.

Pole-Mounted Substations

This type of substation is used to support distribution transformers with capacities up to 250 kVA. Such transformers represent the cheapest, simplest, and smallest form of distribution. All equipment is of outdoor type and installed on the supporting structures of high-voltage distribution lines. A three-pole mechanically operated switch is used to open and close the high-voltage transmission line.

High-tension (HT) fuses are used to protect the high-voltage transmission line. For controlling the low-voltage circuit, low-voltage switches and fuses are provided. Surge arresters are installed on the high-voltage lines to protect the transformer from voltage surges. Pole-mounted substations are grounded at two or more locations.

Transformers with capacities up to 125 kVA are mounted on a two-pole structure, while transformers rated between 125 kVA and 250 kVA are installed on a four-pole structure with an appropriate platform. This type of substation is typically placed in densely populated areas.

They have low maintenance costs, and by deploying a large number of such substations in towns, it is expected that distribution networks can be established at lower cost. However, as the number of transformers increases, the total kVA increases, but load losses do not rise proportionally, leading to an increase in cost per kVA.

Foundation-Mounted Substations

In foundation-mounted substations, all equipment areas are assembled for safety purposes, and the entire substation is enclosed within a fence. The equipment used in such substations is heavy; therefore, the selected site must have good access for heavy transportation.

Advantages of Outdoor Substations

Outdoor substations offer the following main advantages:

  • All equipment in an outdoor substation is visible, making fault location easier.

  • Expansion of outdoor substations is simpler.

  • Construction time required for this type of substation is shorter.

  • Less construction material—such as steel and concrete—is needed.

  • Relatively less construction work is required, and the cost of installing switchgear is low.

  • Maintenance is easy, and adequate spacing between equipment ensures that a fault at one point does not propagate to another.

Disadvantages of Outdoor Substations

  • Outdoor substations require more space.

  • Protective devices must be installed to guard against lightning surge effects.

  • The length of control cables increases, raising the overall cost of the substation.

  • Equipment designed for outdoor substations is more expensive because it requires additional dust and weather protection.

Despite these disadvantages, outdoor substations are widely used in power systems.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
01/29/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.