The 10kV outdoor circuit breaker burned out and the energy storage motor malfunctioned

Felix Spark
04/21/2025

Fault Description

In a certain place, the ZWG - 12 type outdoor vacuum circuit breaker is used for the 10kV circuit breaker. On September 29, 2015, when the circuit breaker in the 172 Zhakou Line interval was to be closed remotely, it was found that the remote closing operation failed. When the operating personnel arrived at the site and inspected, they found scattered iron filings on the ground directly beneath the circuit breaker. After manually energizing the circuit breaker, they operated it and found that the manual opening and closing functions were intact, but the circuit breaker could not complete the electric energy - storage operation. The equipment operation and maintenance personnel promptly reported the defect to the maintenance department. After the maintenance personnel opened the cover plate of the circuit breaker, they found a small pile of iron filings accumulated at the bottom of the circuit breaker mechanism box, and the energy - storage gear of the switch mechanism was severely worn.
 

Cause Analysis

Based on the fault phenomenon that the motor couldn't perform electric energy storage, the maintenance personnel initially suspected a fault in the motor power supply. However, through measurement, this assumption was ruled out. Considering the worn - out energy - storage mechanism at the scene, the maintenance personnel determined that the energy - storage motor had burned out. The measured resistance of the motor winding circuit at the scene was 247 MΩ, confirming the motor burnout.

Regarding the reasons for the motor burnout, generally, there are two possible situations: mechanical faults and electrical faults. A mechanical fault mainly refers to the jamming of the circuit breaker's energy - storage mechanism. This causes the motor to stall during the energy - storage process, leading to motor burnout. In the power system, some circuit breakers are rarely subjected to power - outage operations due to high - level loads. As a result, the mechanisms remain stationary for a long time. Rust and dust accumulation can cause severe jamming of the mechanism. When it reaches a certain degree, the output torque of the energy - storage motor cannot overcome the mechanism's resistance, resulting in motor burnout.

An electrical fault mainly occurs in the motor circuit. When the energy storage is completed, the micro - switch connected in series in the energy - storage circuit fails to disconnect in time. The motor keeps running, but due to the obstruction of the energy - storage holding pawl, the motor stalls and burns out due to overheating.

Fault Handling

The maintenance personnel first removed the motor from the standby interval circuit breaker and replaced the burned - out motor. Subsequently, they manually energized the spring. After the energy - storage process, they measured the micro - switch, and the measurement showed that the micro - switch contacts were in the open state, indicating normal function. When performing the opening and closing operations, they found that there was no jamming in the circuit breaker's energy - storage mechanism.

The maintenance personnel then closed the circuit breaker and carried out electric energy storage. During the energy - storage process, they found that the spring completed energy storage, but the motor kept running. To prevent the motor from burning out again, the maintenance personnel immediately opened the circuit breaker. With the spring energized, they repeatedly tested the on - off state of the micro - switch. The test results showed that regardless of the state of the micro - switch, the motor circuit remained connected. Further inspection of the circuit ruled out the possibility of a parasitic circuit.

When performing electric energy storage again, the maintenance personnel gently pressed the micro - switch with a screwdriver, and the motor stopped running. Based on this, they determined that the micro - switch was damaged. The maintenance personnel replaced it with a new original - factory micro - switch. When the motor was used for energy storage for the first time after the replacement, the motor kept running again when the spring completed energy storage. The maintenance personnel loosened the two fixing screws of the micro - switch, moved the limit switch as close as possible to the gear that presses it, and then fixed it. After that, the electric energy - storage operation returned to normal.

Combining the handling process, the maintenance personnel reached the following fault conclusion: When the spring completed energy storage, due to the small installation margin of the micro - switch itself and the severe wear of the micro - switch compression head, the stroke of the energy - storage mechanism compressing the micro - switch was reduced. The micro - switch was in a critical "virtual open" state. When the circuit breaker was closed, the 220 V AC current broke down the air between the virtual open points of the contacts, connecting the energy - storage circuit, and the motor kept running. When using the resistance gear of a multimeter to measure after opening the circuit breaker, the battery voltage of the multimeter was relatively low and not enough to break down the gap. Therefore, the measurement showed that the micro - switch was in the open state.

 Countermeasures and Suggestions

For this type of fault, it is recommended to strengthen the inspection of this type of outdoor circuit breaker and replace the severely worn micro - switches as soon as possible to avoid motor - burnout accidents. Currently, the design of outdoor circuit breakers lacks a mechanism to connect the energy - storage timeout signal, and there is a lack of monitoring for abnormal energy - storage situations. It is suggested that when conditions permit, the energy - storage timeout signal should be connected to the background alarm system.
Felix Spark

Hey there! I'm an electrical engineer specializing in Failure and Maintenance. I've dedicated my career to ensuring the seamless operation of electrical systems. I excel at diagnosing complex electrical failures, from malfunctioning industrial motors to glitchy power distribution networks. Using state - of - the - art diagnostic tools and my in - depth knowledge, I pinpoint issues quickly. On this platform, I'm eager to share my insights, exchange ideas, and collaborate with fellow experts. Let's work together to enhance the reliability of electrical setups.

Research on the Withstand Voltage Test Method for UHV Oil - immersed Reactors
Research on the Withstand Voltage Test Method for UHV Oil - immersed Reactors
1 Investigation of Insulation Defects in UHV Oil - immersed ReactorsKey challenges in high - voltage oil - filled reactors during operation include insulation faults, iron - core magnetic leakage heating, vibration/noise, and oil leakage.1.1 Insulation FaultsParallel - connected reactors, once connected to the main grid’s primary coil and put into use, operate at full power long - term. Sustained high voltage raises operating temperatures, accelerating aging of coil insulation materials an
Oliver Watts
07/24/2025
Research on the Evaluation Method of Uncertainty in the Verification and Measurement Results of Electronic Voltage Transformers in Power Grids
Research on the Evaluation Method of Uncertainty in the Verification and Measurement Results of Electronic Voltage Transformers in Power Grids
1. IntroductionGrid electronic voltage transformers, as indispensable measuring components in power systems, have their measurement accuracy directly tied to the stable operation and efficient management of power systems. However, in practice, due to the inherent characteristics of electronic components, environmental factors, and limitations of measurement methods, the measurement results of voltage transformers often involve uncertainty. This uncertainty not only impacts the accuracy of power
Oliver Watts
07/24/2025
Test of 10 kV Electronic Current Transformer
Test of 10 kV Electronic Current Transformer
1 Performance AdvantagesIn recent years, electronic current transformers (ECTs) have emerged as a key industry trend. National standards classify them into two types: Active Optical Current Transformers (AOCTs, active hybrid type) and Optical Current Transformers (OCTs, passive optical type). Active hybrid ECTs use low-power electromagnetic transformers and Rogowski coils as core sensing elements (Figure 1).Rogowski coils outperform traditional sensors with non-saturation and wide dynamic ranges
Oliver Watts
07/22/2025
What Tests Are Required for a Qualified Combined Instrument Transformer?
What Tests Are Required for a Qualified Combined Instrument Transformer?
Hi everyone, I’m Oliver, and I’ve been working in the instrument transformer industry for almost eight years now. From a complete newbie to someone who can now handle things independently, I’ve participated in dozens of combined instrument transformer inspections over the years.Today, I’d like to share with you: What tests must a qualified combined instrument transformer go through before leaving the factory or being put into operation? After all, it's a very critical pie
Oliver Watts
07/21/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!