• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Interlocking system for switchgear automation in double busbar substation

Edwiin
Field: Power switch
China

  1. The tripping of all circuit breakers (CBs) by protective relays is unrestricted.

  2. The opening command for all circuit breakers, except for the busbar coupler circuit breaker, is unrestricted.

  3. An opening command cannot be issued for the busbar coupler circuit breaker under the following circumstances:

    1. Both busbar disconnect switches (DSs) of any feeder are closed.

    2. Any busbar disconnect switch or sectionalizing disconnect switch is in the transition state.

  4. A closing command cannot be given for a circuit breaker when its associated line disconnect switch or busbar disconnect switch is in the transition state.

  5. A line disconnect switch can only be operated when its associated circuit breaker and feeder earthing switch (ES) are open.

  6. A feeder earthing switch can only be operated when its associated line disconnect switch (if applicable) and busbar disconnect switch are open.

  7. A busbar disconnect switch can be operated when its circuit breaker, busbar earthing switch, feeder earthing switch, and the other busbar disconnect switch are all open (except for item 8).

  8. If a busbar disconnect switch is closed, the second busbar disconnect switch can only be operated when the relevant busbar sections are connected through the busbar coupler circuit breaker.

  9. A busbar earthing switch can only be operated when the busbar disconnect switches and the busbar sectionalizing disconnect switch on the associated busbar are open.

  10. A busbar sectionalizing disconnect switch can only be operated when all the busbar disconnect switches and the busbar earthing switch on the same side of this sectionalizing disconnect switch are open.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.