• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Nyquist Plot: What is it? (And How To Draw One)

Electrical4u
Field: Basic Electrical
0
China

What Is A Nyquist Plot

What is a Nyquist Plot?

A Nyquist plot (or Nyquist Diagram) is a frequency response plot used in control engineering and signal processing. Nyquist plots are commonly used to assess the stability of a control system with feedback. In Cartesian coordinates, the real part of the transfer function is plotted on the X-axis, and the imaginary part is plotted on the Y-axis.

The frequency is swept as a parameter, resulting in a plot based on frequency. The same Nyquist plot can be described using polar coordinates, where the gain of the transfer function is the radial coordinate, and the phase of the transfer function is the corresponding angular coordinate.



What is Nyquist Plot



The stability analysis of a feedback control system is based on identifying the location of the roots of the characteristic equation on the s-plane.

The system is stable if the roots lie on the left-hand side of the s-plane. The relative stability of a system can be determined by using frequency response methods – such as the Nyquist plot, Nichols plot, and Bode plot.

The Nyquist stability criterion is used to identify the presence of roots of a characteristic equation in a specified region of the s-plane.

To understand a Nyquist plot we first need to learn about some of the terminologies. Note that a closed path in a complex plane is called a contour.

Nyquist Path or Nyquist Contour

The Nyquist contour is a closed contour in the s-plane which completely encloses the entire right-hand half of the s-plane.

In order to enclose the complete RHS of the s-plane, a large semicircle path is drawn with a diameter along jω axis and center at the origin. The radius of the semicircle is treated as Nyquist Encirclement.

Nyquist Encirclement

A point is said to be encircled by a contour if it is found inside the contour.

Nyquist Mapping

The process by which a point in the s-plane is transformed into a point in the F(s) plane is called mapping and F(s) is called the mapping function.

How to Draw Nyquist Plot

A Nyquist plot can be drawn using the following steps:

  • Step 1 – Check for the poles of G(s) H(s) of the jω axis including that at the origin.

  • Step 2 – Select the proper Nyquist contour – a) Include the entire right half of the s-plane by drawing a semicircle of radius R with R tends to infinity.

  • Step 3 – Identify the various segments on the contour with reference to the Nyquist path

  • Step 4 – Perform the mapping segment by segment by substituting the equation for the respective segment in the mapping function. Basically, we have to sketch the polar plots of the respective segment.

  • Step 5 – Mapping of the segments are usually mirror images of mapping of the respective path of +ve imaginary axis.

  • Step 6 – The semicircular path which covers the right half of s plane generally maps into a point in G(s) H(s) plane.

  • Step 7- Interconnect all the mapping of different segments to yield the required Nyquist diagram.

  • Step 8 – Note the number of clockwise encirclements about (-1, 0) and decide stability by N = Z – P


is the Open loop transfer function (O.L.T.F)


is the Closed loop transfer function (C.L.T.F)
N(s) = 0 is the open loop zero and D(s) is the open loop pole
From a stability point of view, no closed loop poles should lie on the RH side of the s-plane. Characteristics equation 1 + G(s) H(s) = 0 denotes closed-loop poles .

Now as 1 + G(s) H(s) = 0 hence q(s) should also be zero.

Therefore, from the stability point of view zeroes of q(s) should not lie in the RHP of the s-plane.
To define the stability entire RHP (Right-Hand Plane) is considered. We assume a semicircle that encloses all points in the RHP by considering the radius of the semicircle R tends to infinity. [R → ∞].

The first step to understanding the application of the Nyquist criterion in relation to the determination of stability of control systems is mapping from the s-plane to the G(s) H(s) – plane.

s is considered an independent complex variable and the corresponding value of G(s) H(s) is the dependent variable plotted in another complex plane called the G(s) H(s) – plane.

Thus for every point in the s-plane, there exists a corresponding point in G(s) H(s) – plane. During the process of mapping, the independent variable s is varied along a specified path in the s-plane, and the corresponding points in G(s)H(s) plane are joined. This completes the process of mapping from the s-plane to the G(s)H(s) – plane.

Nyquist stability criterion says that N = Z – P. Where, N is the total no. of encirclement about the origin, P is the total no. of poles and Z is the total no. of zeroes.
Case 1: N = 0 (no encirclement), so Z = P = 0 and Z = P
If N = 0, P must be zero therefore the system is stable.
Case 2: N > 0 (clockwise encirclement), so P = 0, Z ≠0 and Z > P
In both cases the system is unstable.
Case 3: N < 0 (counter-clockwise encirclement), so Z = 0, P ≠0 and P > Z
The system is stable.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.