• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Trigonometric Fourier Series

Electrical4u
Field: Basic Electrical
0
China

What Is Trigonometric Fourier Series

We have already discussed the Fourier series in exponential form. In this article we will discuss another form of Fourier series i.e. Trigonometric Fourier series.

Fourier series representation in Trigonometric form

Fourier series in trigonometric form can be easily derived from its exponential form. The complex exponential Fourier series representation of a periodic signal x(t) with fundamental period To is given by

Since sine and cosine can be expressed in exponential form. Thus by manipulating the exponential Fourier series, we can obtain its Trigonometric form.

The trigonometric Fourier series representation of a periodic signal x (t) with fundamental period T, is given by

Where ak and bk are Fourier coefficients given by

a0 is the dc component of the signal and is given by

Properties of Fourier series

1. If x(t) is an even function i.e. x(- t) = x(t), then bk = 0 and

2. If x(t) is an even function i.e. x(- t) = – x(t), then a0 = 0, ak = 0 and

3. If x(t) is half symmetric function i.e. x (t) = -x(t ± T0/2), then a0 = 0, ak = bk = 0 for k even,

4. Linearity

5. Time shifting

6. Time reversal

7. Multiplication

8. Conjugation

9. Differentiation

10. Integration

11. Periodic Convolution

Relationship between coefficients of exponential form and coefficients of trigonometric form


When x (t) is real, then a, and b, are real, we have

Effect of Shifting Axis of the Signal

  • On shifting the waveform to the left right with respect to the reference time axis t = 0 only the phase values of the spectrum changes but the magnitude spectrum remains same.

  • On shifting the waveform upward or downward w.r.t time axis changes only the DC value of the function.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.