Megger | Working Principle Types History Uses of Megger

Electrical4u
Field: Basic Electrical
0
China

What Is Megger

History of Megger

The device is being used since 1889, popularity raised during 1920s since the long back device is same in its uses and purpose of testing, few real improvements appeared in recent years with its design and quality of tester. Now high-quality options are available which are easy to use and quite safe.

What is Megger?

Insulation resistance IR quality of an electrical system degrades with time, environment condition, i.e., temperature, humidity, moisture and dust particles. It also gets impacted negatively due to the presence of electrical and mechanical stress, so it’s become very necessary to check the IR (Insulation resistance) of equipment at a constant regular interval to avoid any measure fatal or electrical shock.

electronics megger

Uses of Megger

The device enable us to measure electrical leakage in wire, results are very reliable as we shall be passing electric current through device while we are testing. The equipment basically uses for verifying the electrical insulation level of any device such as motors, cables, generators, windings, etc. This is a very popular test being carried out since very long back. Not necessary it shows us exact area of electrical puncture but shows the amount of leakage current and level of moisture within electrical equipment/winding/system.

Types of Megger

This can be separated into mainly two categories:-

  • Electronic Type (Battery Operated)

  • Manual Type (Hand Operated)

But there is another types of megger which is motor operated type which does not use battery to produce voltage it requires external source to rotate a electrical motor which in turn rotates the generator of the megger.

electronics megger

Electronic Type Megger

Important parts:-

  • Digital Display :- A digital display to show IR value in digital form.

  • Wire Leads :- Two nos of wire leads for connecting megger with electrical external system to be tested.

  • Selection Switches :- Switches use to select electrical parameters ranges.

  • Indicators :- To indicates various parameters status i.e. On-Off. For Example Power, hold, Warning, etc.

Note: – Above construction is not similar for every megger, it difference appears manufacture to manufacture but basic construction and operation are same for all.

Advantages of Electronic Type Megger

  • Level of accuracy is very high.

  • IR value is digital type, easy to read.

  • One person can operate very easily.

  • Works perfectly even at very congested space.

  • Very handy and safe to use.

Disadvantages of Electronic Type Megger

  • Require an external source of energy to energies i.e. Dry cell.

  • Costlier in market.

Hand Operated Megger

hand operated megger
Important parts:-
Analog display:- Analog display provided on front face of tester for IR value recording.
Hand Crank:- Hand crank used to rotate helps to achieve desired RPM required generate voltage which runs through electrical system.
Wire Leads:- Used same as in electronic tester i.e. For connecting tester with electrical system.

Advantages of Hand Operated Megger

  • Still keeps important in such high-tech world as it’s an oldest method for IR value determination.

  • No external source required to operate.

  • Cheaper available in market.

Disadvantages of Hand Operated Megger

  • At least 2 person required to operate i.e. one for rotation of crank other to connect megger with electrical system to be tested.

  • Accuracy is not up to the level as it’s varies with rotation of crank.

  • Require very stable placement for operation which is a little hard to find at working sites.

  • Unstable placement of tester may impact the result of tester.

  • Provides an analog display result.

  • Require very high care and safety during use of the same.

Construction of Megger

Circuit Construction features :-
megger principle

  • Deflecting and Control coil : Connected parallel to the generator, mounted at right angle to each other and maintain polarities in such a way to produced torque in opposite direction.

  • Permanent Magnets : Produce magnetic field to deflect pointer with North-South pole magnet.

  • Pointer : One end of the pointer connected with coil another end deflects on scale from infinity to zero.

  • Scale : A scale is provided in front-top of the megger from range ‘zero’ to ‘infinity’, enable us to read the value.

  • D.C generator or Battery connection : Testing voltage is produced by hand operated DC generator for manual operated Megger. Battery / electronic voltage charger is provided for automatic type Megger for same purpose.

  • Pressure Coil Resistance and Current Coil Resistance : Protect instrument from any damage because of low external electrical resistance under test.

Working Principle of Megger

  • Voltage for testing produced by hand operated megger by rotation of crank in case of hand operated type, a battery is used for electronic tester.

  • 500 Volt DC is sufficient for performing test on equipment range up to 440 Volts.

  • 1000 V to 5000 V is used for testing for high voltage electrical systems.

  • Deflecting coil or current coil connected in series and allows flowing the electric current taken by the circuit being tested.

  • The control coil also known as pressure coil is connected across the circuit.

  • Current limiting resistor (CCR and PCR) connected in series with control and deflecting coil to protect damage in case of very low resistance in external circuit.

  • In hand operated megger electromagnetic induction effect is used to produce the test voltage i.e. armature arranges to move in permanent magnetic field or vice versa.

  • Where as in electronic type megger battery are used to produce the testing voltage.

  • As the voltage increases in external circuit the deflection of pointer increases and deflection of pointer decreases with a increases of current.

  • Hence, resultant torque is directly proportional to voltage and inversely proportional to current.

  • When electrical circuit being tested is open, torque due to voltage coil will be maximum and pointer shows ‘infinity’ means no shorting throughout the circuit and has maximum resistance within the circuit under test.

  • If there is short circuit pointer shows ‘zero’, which means ‘NO’ resistance within circuit being tested.

Work philosophy based on ohm-meter or ratio-meter. The deflection torque is produced with megger tester due to the magnetic field produced by voltage and current, similarly like ‘Ohm’s Law’.
The torque of the megger varies in a ration with V/I, (Ohm’s Law:- V = IR or R = V/I). Electrical resistance to be measured is connected across the generator and in series with deflecting coil.
Produced torque shall be in opposite direction if current supplied to the coil.

  • High Resistance = No Current :- No current shall flow through deflecting coil, if resistance is very high i.e. infinity position of pointer.

  • Small Resistance = High Current :- If circuit measures small resistance allows a high electric current to pass through deflecting coil, i.e. produced torque make the pointer to set at ‘ZERO’.

  • Intermediate Resistance = Varied Current :- If measured resistance is intermediate, produced torque align or set the pointer between the range of ‘ZERO to INIFINITY’.

Connection Diagram of Megger for Testing

megger
megger

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.