• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Protection of Meters

Electrical4u
Field: Basic Electrical
0
China

What Is The Protection Of Meters

When we measure an electrical signal there very often may be a chance of over current through the meter. This may be due to following reasons.

  • The meter may be connected wrongly to the circuit.

  • The rating of the meter is selected wrongly for the measurement.

  • Occurrences of over current in the circuit itself during measurement.

Over current causes overheating in the meter which may ultimately lead to a permanent damage to the meter. The reasons of the over current cannot be avoided 100% although it is convenient to protect the meter from the effect of over current. This is done by using semiconductor diode of suitable rating.

Whenever a meter is con nected in the circuit to measure an electrical signal, there must be a voltage drop across it. If the current through the meter is increased beyond safety limit, the voltage drop also crosses the rated limit. Suppose the rated voltage drop limit of the meter is 0.6 volt. Now, let us connect a diode across the meter, whose forward barrier voltage is 0.6 volt. Now, if due to excess current through the meter, if the voltage drop across the meter becomes more than 0.6 volt, the diode becomes short-circuited, since this excess voltage also appears across the diode.

As soon as the diode is short-circuited, the meter current is diverted through the diode. As result, the meter is being protected from excess heating. If only one diode is used it is called Single Diode Protection.
single diode meter protection

If two diodes are connected across the meter in opposite direction, it is called double diode protection. This arrangement protects the meter for both directions of current.
double diode meter protection

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.