• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What is the Differential Protection of Transformers?

Encyclopedia
Field: Encyclopedia
0
China

What is the  Differential Protection of Transformers?

Differential Protection Definition

The differential protection of transformer is an important relay protection method, which is used to detect the faults inside the transformer, such as winding short circuit, turn short circuit and so on. Differential protection determines whether there is a fault by comparing the difference in current on both sides of the transformer.

ac08c2d8-2533-42f7-a426-9f567fd87029.jpg

Principle of differential protection

Differential protection is based on a basic principle: under normal operating conditions, the incoming and outgoing currents on both sides of the transformer should be balanced. If a fault occurs inside the transformer, such as a short circuit in the winding, an unbalanced current will be generated in the differential circuit. The differential protective relay detects this unbalanced current to trigger the protective action.

Disposition

Current transformers (CTs) : Current transformers are installed on each side of the transformer to measure current.

Differential relay: The differential relay receives the current signal from the CTs and compares it.

Ratio braking characteristics: Differential relays usually have ratio braking characteristics, that is, the protective action value increases as the unbalanced current increases in the event of an external fault to prevent misoperation.

Operation process

Install current transformer

Install the current transformer on the primary side and the secondary side of the transformer.The polarity of the CTs needs to be properly connected to ensure the correct current flow.

Configuration differential relay

Set the operating threshold of the differential relay.Adjust the parameters of the ratio braking characteristics to suit the specific situation of the transformer.

Monitoring unbalance current

A differential relay continuously monitors the difference in current flowing into and out of the transformer.When the unbalance current exceeds the set threshold, the differential protection will operate.Trigger protection action.When an internal fault is detected, the differential protection triggers a trip, disconnecting the faulty transformer from the grid.

Matters needing attention

Polarity connection: Ensure that the polarity of the current transformer is correctly connected, otherwise it will cause protection misoperation.

Ratio braking characteristics: The ratio braking characteristics are set correctly to prevent misoperation in case of external failure.

Current transformer saturation: In extreme cases such as short circuits, the CTs may become saturated, resulting in protective misoperation.

Winding wiring: Ensure that the winding wiring is correct to avoid unbalanced current.

Maintenance and verification: Maintain and verify differential protection regularly to ensure its accuracy and reliability.

Advantages of differential protection

Fast response: Can quickly detect the transformer internal fault.

Highly selective: It only operates when a fault occurs inside the transformer and is selective to external faults.

High sensitivity: reliable operation even in case of minor internal faults.

Limitations of differential protection

External failure: In the event of an external failure, the differential protection may be affected by an unbalanced current, resulting in misoperation.

CTs saturation: Under extreme high current conditions, CTs may become saturated, affecting the accuracy of protection.

Maintenance and verification

Periodic verification: Periodically verify the differential protection system to ensure that its performance meets the requirements.

Simulation test: Perform simulated fault tests to verify the response capability of the protection system.

CTs maintenance: Periodically check the operating status of the CTs to ensure its accuracy and reliability.

Give a tip and encourage the author!

Recommended

Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Reclosing Charge Time: Why Does Reclosing Require Charging? What Effects Does Charging Time Have?
1. Function and Significance of Reclosing ChargingReclosing is a protective measure in power systems. After faults such as short circuits or circuit overloads occur, the system isolates the faulty circuit and then restores normal operation through reclosing. The function of reclosing is to ensure continuous operation of the power system, improving its reliability and safety.Before performing reclosing, the circuit breaker must be charged. For high-voltage circuit breakers, the charging time is g
12/15/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.