• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Loss of Field or Excitation Protection of Alternator or Generator

Electrical4u
Field: Basic Electrical
0
China

What Is The Excitation Protection Of Alternator Or Generator

Loss of field or excitation can be caused in the generator due to excitation failure. In larger sized generator, energy for excitation is often taken from a separate auxiliary source or from a separately driven DC generator. The failure of auxiliary supply or failure of driving motor can also cause the loss of excitation in a generator. Failure of excitation that is failure of field system in the generator makes the generator run at a speed above the synchronous speed.
In that situation the generator or
alternator becomes an induction generator which draws magnetizing current from the system. Although this situation does not create any problem in the system immediately but over loading of the stator and overheating of the rotor due to continuous operation of the machine in this mode may create problems in the system in long-run. Therefore special care should be taken for rectifying the field or excitation system of the generator immediately after failure of that system. The generator should be isolated from rest of the system till the field system is properly restored.

There are mainly two schemes available for protection against loss of field or excitation of a generator. In 1st scheme, we use an undercurrent relay connected in shunt with main field winding circuit. This relay will operate if the excitation current comes below its predetermined value. If the relay is to operate for complete loss of field along, it must have a setting lies well below the minimum excitation current value which can be 8% of the rated full load current. Again when loss of field occurs due to failure of exciter but not due to problem in the field circuit (field circuit remains intact) there will be an induced current at slip frequency in the field circuit. This situation makes the relay to pick up and drop off as per slip frequency of the induced current in the field. This problem can be overcome in the following manner.

loss of field protection

In this case a setting of 5% of normal of full load current is recommended. There is a normally closed contact attached with the undercurrent relay. This normally closed contact remains open as the relay coil is energized by shunted excitation current during normal operation of the excitation system. As soon as there is any failure of excitation system, the relay coil becomes de-energized and the normally closed contact closes the supply across the coil of timing relay T1.

As the relay coil is energized, the normally open contact of this relay T1 is closed. This contact closes the supply across another timing relay T2 with an adjustable pickup time delay of 2 to 10 seconds. Relay T1 is time delayed on drop off to stabilize scheme again slip frequency effect. Relay T2 closes its contacts after the prescribed time delay to either shut down the set or initiate an alarm. It is time delayed on pickup to prevent spurious operation of the scheme during an external fault.
loss of excitation protectionloss of field protection of alternatorFor larger generator or alternator, we use a more sophisticated scheme for that purpose. For larger machines, it is recommended to trip the machine after a certain prescribed delay in presence of swing condition resulting from loss of field. In addition to that there must be subsequent load shedding to maintain stability of the system. In this scheme of protection, an automatic imposition of load shedding to the system is also inherently required if the field is not restored within the described time delay. The scheme comprises an offset mho relay, and an instantaneous under voltage relay. As we have said earlier that it is not always required to isolate the generator immediately in the event of loss of field, unless there is a significant disturb in system stability.
We know that system voltage is the main indication of system stability. Therefore the offset mho relay is arranged to shut the machine down instantaneously when operation of generator is accompanied by a system voltage collapse. The drop in system voltage is detected by an under
voltage relay which is set to approximately 70 % of normal rated system voltage. The offset mho relay is arranged to initiate load shedding to the system up to a safe value and then to initiate a master tripping relay after a predetermined time.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.