• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Inverse Time Relay | Definite Time Lag Relay

Electrical4u
Field: Basic Electrical
0
China

What Is Inverse Time Relay

In this type of relays, the time of operation depends upon the magnitude of actuating quantity. If the magnitude of actuating quantity is very high, the relay operation is very fast. In other words, the relay operating time that is time delay in the relay is inversely proportional to the magnitude of actuating quantity.
The general characteristics of an inverse time relay is shown are in figure below.
inverse time relay curve

Here, in the graph it is clear that, when, actuating quantity is OA, the operating time of the relay is OA’, when actuating quantity is OB, the relay operating time is OB’ and when actuating quantity is OC, the relay operating quantity is OC’.
In the graph above, it is also observed that, when actuating quantity is less than OA, the relay operating time becomes infinity, which means for actuating quantity less than OA, the relay does not at all actuate. This minimum value of actuating quantity for which a relay initiates its operation is known as pick up value of actuating quantity. Here it is denoted as OA.
It is also seen from the graph that, when actuating quantity approaches to infinity along x axis the operating time does not approach to zero. The curve approaches to an approximately constant operating time. This is approximately minimum time required to operate the relay.

The inverse time relay, where the actuating quantity is current, is known as inverse current relay.
In this type of relay, the inverse time is achieved by attaching some mechanical accessories in the relay.
Inverse time delay is achieved in induction disc relay by providing a permanent magnet in such a way, that, when disc rotates, it cuts the
flux of permanent magnet. Due to this, current is induced in the disc which slows down the movement of the disc. A solenoid relay can be made inverse time relay, by providing a piston and an oil dash-pot. A piston, attached to the moving iron plunger, is immersed in oil in a dash-pot. When the solenoid relay is actuated, the piston moves upwards along with iron plunger.

Viscosity of oil slows the upward movement of plunger. The speed of this upward movement against gravity also depends upon how strongly the solenoid attracts the iron plunger. This attraction force of the solenoid depends upon the magnitude of actuating current. Hence, time of operation of relay is inversely proportional to actuating current.

Definite Time Lag Relay

During relay coordination in electrical power system protection scheme, there is some time intentionally required, to operate some specific relays after some specific time delays. Definite time lag relays are those which operate after a specific time.
The time lag between instant when the actuating current crosses the pickup level and the instant when relay contacts finally closed, is constant. This delay does not depend up on magnitude of actuating quantity. For all actuating quantity, above pick up values, the relay operating time is constant.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.