What are the advantages and disadvantages of single-phase reclosing and three-phase reclosing?

Echo
Field: Transformer Analysis
China

Single-Phase Reclosing

Advantage:

When a single-phase-to-ground fault occurs on a line and three-phase auto-reclosing is applied, it results in higher switching overvoltages compared to single-phase reclosing. This is because three-phase tripping interrupts the current at zero-crossing, leaving residual charge voltages on the unfaulted phases—approximately equal to the peak phase voltage. Since the de-energized interval during reclosing is relatively short, the voltage on these unfaulted phases does not decay significantly, leading to substantial switching overvoltage upon reclosure. In contrast, with single-phase reclosing, the voltage on the faulted phase at the moment of reclosure is typically only about 17% of nominal (due to capacitive voltage division along the line), thus avoiding significant switching overvoltage. Long-term operational experience with three-phase reclosing in 110 kV and 220 kV networks shows that switching overvoltage issues are generally not severe on medium- and short-length lines.

Disadvantage:

When single-phase auto-reclosing is used, non-full-phase operation occurs. In addition to requiring special considerations for pilot protection, this significantly affects the setting and coordination of zero-sequence current protection, thereby preventing zero-sequence current protection on medium- and short-length lines from functioning effectively.
Three-Phase Reclosing

Advantage:

When three-phase auto-reclosing is used, the tripping circuits of all protective relays can directly actuate the circuit breaker. However, when single-phase auto-reclosing is employed, all pilot protections, phase-to-phase distance protections, zero-sequence current protections, etc.—except those inherently possessing phase-selection capability—must be controlled by the phase-selection element of the single-phase recloser before they can operate the circuit breaker.

Disadvantage:

When three-phase auto-reclosing is used, under the worst-case scenario, reclosure may occur onto a three-phase short-circuit fault. For certain lines where stability studies indicate that such reclosure must be avoided, a simple phase-to-phase fault detection element can be added to the three-phase reclosing scheme. This element prevents reclosing for phase-to-phase faults while still allowing reclosure for single-phase faults.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.