Out of phase in generator circuit breaker (GCB)

Edwiin
Field: Power switch
China

An out-of-phase condition transpires when a generator circuit breaker (GCB) closing operation is executed precisely at the moment when there is a lack of synchronism between the voltage phasors of the generator on one side of the GCB and those of the external grid on the other side. Another common scenario is when a generator runs in an out-of-phase state due to system instability, necessitating the tripping of the GCB.

The severity of such an interruption is directly related to the out-of-phase angle δ. Given that the generator faces significant risks when δ exceeds 90°, protective relays are typically configured to trip at around δ = 90°. Standardized out-of-phase transient recovery voltage (TRV) values are established based on a 90° out-of-phase angle at the rated voltage. It is worth noting that for smaller generator units, larger out-of-phase angles can still occur.

When the out-of-phase angle δ reaches 90°, the current is approximately 50% of the fault current supplied by the system. On the voltage side, the GCB is subjected to a TRV with a rate of rise of the recovery voltage (RRRV) roughly equivalent to that in a system-source fault, but its peak value is nearly twice as high. The out-of-phase current specified in the standard is indeed set at half of the system source-fault current.

The figure illustrates the standardized TRV waveforms for various generator faults, juxtaposed with the TRV of a 100% fault for a 24 kV GCB, providing a clear visual comparison of the electrical characteristics under different fault conditions.

Give a tip and encourage the author!

Recommended

Main Transformer Accidents and Light Gas Operation Issues
1. Accident Record (March 19, 2019)At 16:13 on March 19, 2019, the monitoring background reported a light gas action of No. 3 main transformer. In accordance with the Code for Operation of Power Transformers (DL/T572-2010), operation and maintenance (O&M) personnel inspected the on-site condition of No. 3 main transformer.On-site confirmation: The WBH non-electrical protection panel of No. 3 main transformer reported a Phase B light gas action of the transformer body, and the reset was ineff
02/05/2026
Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026