• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Railway 10kV Power Through Lines: Design & Operation Requirements

Edwiin
Field: Power switch
China

The Daquan Line has a large power load, with numerous and scattered load points along the section. Each load point has a small capacity, with an average of one load point every 2-3 km, so two 10 kV power through lines should be adopted for power supply. High-speed railways use two lines for power supply: primary through line and comprehensive through line. The power sources of the two through lines are taken from the dedicated bus sections fed by the voltage regulators installed in each power distribution room. Communication, signaling, integrated dispatching systems and other facilities related to train operation along the line are mainly supplied by the primary through line and standby supplied by the comprehensive power through line.

1. Route of Power Line Circuits

In conventional-speed railways, the two 10 kV power lines, automatic block signaling power lines and power through lines are all overhead lines (some sections limited by terrain can be converted to cable lines), and the line routes are basically outside the railway clearance. During operation, the automatic block signaling lines usually adopt LGJ-50mm² overhead lines, which supply power for primary loads such as railway signaling, communication equipment and 5T systems. The through system mainly adopts LGJ-70mm² overhead lines, which also supply power for primary loads including railway signaling, communication equipment and 5T systems, and at the same time provide effective power supply for railway sections and various facilities. However, since overhead lines are the main operating lines in use, they have small capacitance and small single-phase grounding current. When a ground fault occurs, the arc can be automatically extinguished. Therefore, the ungrounded neutral point mode is usually selected in circuit design.

2. Requirements for Switching On/Off of Automatic Reclosing and Standby Power Auto-Input Functions in Power Distribution Rooms for High-Speed and Conventional-Speed Railways

Due to the differences in the routes and laying methods of power lines between high-speed railways and conventional-speed railways, their requirements for the switching on/off functions of line standby power auto-input and automatic reclosing in power distribution rooms are also different.

Most of the power lines along high-speed railways are laid with cables. Once a fault occurs, most of them are permanent faults. Activating standby power auto-input or automatic reclosing under permanent fault conditions will only aggravate the secondary impact on circuit breakers and other equipment, and even lead to power supply breakdown, thereby expanding the power outage range. Therefore, standby power auto-input or automatic reclosing should generally not be activated for high-speed railway power lines. After a fault occurs, due to the dual-circuit power supply, equipment inspection should be arranged when one power source is available, and power supply should be restored only after finding the fault cause to ensure safe power supply of equipment.

Most of the conventional-speed railway power lines are overhead lines, erected along the railway line in the open air. Limited by terrain and affected by natural weather such as rain, snow, wind, fog and lightning strikes, most faults are instantaneous. For instantaneous faults, standby power auto-input or automatic reclosing functions should be set to deal with instantaneous faults conveniently and ensure uninterrupted power supply for railways.

3. Conclusion

With the continuous development of the railway system, the 10 kV power through and automatic block signaling lines of power distribution rooms involved in the railway power supply system are changing in terms of name, circuit and laying method, and the operation mode is also changing accordingly. However, no matter how the changes are made, the purpose is to ensure the safe, stable and reliable operation of railway power supply.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.