Sag in a Transmission Line: What is it? (And How To Calculate it)

Electrical4u
Field: Basic Electrical
0
China

what is sag in transmission line

What is Sag in a Transmission Line?

In a transmission line, sag is defined as the vertical difference in level between points of support (most commonly transmission towers) and the lowest point of the conductor. The calculation of sag and tension in a transmission line depends on the span of the overhead conductor.

Span having equal level supports (i.e. towers of the same height) is called level span. Conversely, when the span has unequal levels of support, this is known as unequal level span.

Consider a transmission line conductor AOB suspended freely between level supports A and B at the same level (equal span). The shape of the conductor is a parabola and the lowest point of the conductor is O.

overhead conductor sagIn the above overhead conductor AOB, S is the sag when measured vertically.

Why is Sag Mandatory in Transmission Line Conductors?

Sag is mandatory in transmission line conductor suspension. The conductors are attached between two supports with the perfect value of sag.

This is because it protects the conductor from excessive tension. In order to permit a safe level of tension in the conductor, conductors are not fully stretched; rather they are allowed to have sagged.

If the conductor is stretched fully during installation, wind exerts pressure on the conductor, hence the conductor gets a chance to be broken or detached from its end support. Thus sag is allowed to have during conductor suspension.

Some important points to note:


    1. When the same leveled two supports hold the conductor, a bent shape arises in the conductor. Sag is very small with respect to the span of the conductor.

    2. The Sag span curve is parabolic.

    3. The tension in each point of the conductor acts always tangentially.

  1. Again the horizontal component of the tension of the conductor is constant throughout conductor length.

  2. The tension at supports is nearly equal to the tension at any point in the conductor.

How to Calculate Sag in a Transmission Line

When calculating sag in a transmission line, two different conditions need to be considered:

  1. When supports are at equal levels

  2. When supports are not at equal levels

The formula to calculate sag changes based on whether the support levels (i.e. the transmission towers holding up the overhead conductor) are at the same level.

Sag calculation for supports are at equal levels
Suppose, AOB is the conductor. A and B are points of supports. Point O is the lowest point and the midpoint.
Let, L = length of the span, i.e. AB
w is the weight per unit length of the conductor
T is the tension in the conductor.
We have chosen any point on the conductor, say point P.
The distance of point P from the Lowest point O is x.
y is the height from point O to point P.

Equating two moments of two forces about point O as per the figure above we get,
sag equation
sag formulaSag calculation for supports are at unequal levels
sag calculation for supports are at unequal levelsSuppose AOB is the conductor that has point O as the lowest point.
L is the Span of the conductor.
h is the difference in height level between two supports.
x1 is the distance of support at the lower level point A from O.
x2 is the distance of support at the upper-level point B from O.
T is the tension of the conductor.
w is the weight per unit length of the conductor.
Now,
tension and sag formula
tension and sag calculationSo, having calculated the value of x1 and x2, we can easily find out the value of sag S1 and sag S2.

The above formula is used to calculate sag when the conductor is in still air and ambient temperature is normal. Hence the weight of the conductor is its own weight.

What is the Effect of Ice and Wind on Sag?

Some of the effects of ice and wind on sag include:

  • The weight per unit length of the conductor is changed when the wind blows at a certain force on the conductor and ice accumulate around the conductor.

  • Wind force acts on the conductor to change the conductor self-weight per unit length horizontally in the direction of the airflow.

  • Ice loading acts on the conductor to change the conductor self-weight per unit length vertically downward.

  • Considering wind force and ice loading both at a time, the conductor will have a resultant weight per unit length.

  • The resultant weight will create an angle with the ice loading down ward direction.

Let us assume, w is the weight of the conductor per unit length.
wi is the weight of ice per unit length
wi= density of ice × volume of ice per unit length

sagww is the force of wind per unit length
ww = wind pressure per unit area × projected area per unit length
So, the total weight of the conductor per unit length is


The sag in the conductor is given by

So the vertical sag

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.