Synchronous Condenser

Electrical4u
Field: Basic Electrical
0
China

What Is Synchronous Condenser

Like capacitor bank, we can use an overexcited synchronous motor to improve the poor power factor of a power system. The main advantage of using synchronous motor is that the improvement of power factor is smooth.
When a synchronous motor runs with over-excitation, it draws leading
current from the source. We use this property of a synchronous motor for the purpose.

Here, in a three-phase system, we connect one three-phase synchronous motor and run it at no load.
three phase synchronous motorSuppose due to a reactive load of the power system the system draws a current IL from the source at a lagging angle θL in respect of voltage. Now the motor draws a IM from the same source at a leading angle θM. Now the total current drawn from the source is the vector sum of the load current IL and motor current IM. The resultant current I drawn from the source has an angle θ in respect of voltage. The angle θ is less than angle θL. Hence power factor of the system cosθ is now more than the power factor cosθL of the system before we connect the synchronous condenser to the system.

The synchronous condenser is the more advanced technique of improving power factor than a static capacitor bank, but power factor improvement by synchronous condenser below 500 kVAR is not economical than that by a static capacitor bank. For major power network we use synchronous condensers for the purpose, but for comparatively lower rated systems we usually employ capacitor bank.

The advantages of a synchronous condenser are that we can control the power factor of system smoothly without stepping as per requirement. In case of a static capacitor bank, this fine adjustments of power factor cannot be possible rather a capacitor bank improves the power factor stepwise.
The short circuit withstand-limit of the
armature winding of a synchronous motor is high.

Although, synchronous condenser system has some disadvantages. The system is not silent since the synchronous motor has to rotate continuously.
An ideal load less synchronous motor draws leading
current at 90o(electrical).

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.