Shunt Reactor Function, Calculation, and Compensation

Electrical4u
Field: Basic Electrical
0
China

What Is A Shunt Reactor

What is Shunt Reactor

A shunt reactor is a piece of electrical equipment used in high voltage power transmission systems to stabilize the voltage during load variations. A traditional shunt reactor has a fixed rating and is either connected to the transmission line all the time or switched in and out depending on the load.

A three phase shunt reactor is generally connected to 400KV or above electrical bus system for capacitive reactive power compensation of the power system and to control dynamic over voltage occurring in the system due to load rejection.

The shunt reactor should be capable of withstanding maximum continuous operating voltage (5% higher the rated voltage in case of 400 KV system) under normal power frequency variation without exceeding the top spot temperature of 150oC at any part of the shunt reactor.

The shunt reactor should be of gapped core type or magnetically shielded air core type. Both of these designs help to maintain the impedance of the reactor fixed. The impedance should be maintained at a constant value for avoiding harmonic current generated due to the system over voltage.
shunt reactor
The shunt reactor has mainly core losses during its normal operating condition. So, care should be taken for minimizing the core losses during design.

Measurement of Losses in Shunt Reactor

We should measure the losses of a shunt reactor at rated voltage and frequency. But for very high voltage shunt reactor, it may be difficult to arrange such a high test voltage during measurement of losses. This difficulty can be overcome, by measuring the losses of the shunt reactor at any voltage lower than the system voltage of the reactor. Then this measured loss is multiplied by the square of the ratio of rated current to the current of the reactor at applied reduced test voltage to obtain the loss at rated voltage.


As the power factor of the shunt reactor is very low, loss measurement of shunt reactor by conventional wattmeter is not very reliable, instead of bridge method of measurement may be adopted for better accuracy.
This test can not segregate the losses in various parts of the reactor. To avoid, correction of test result for a reference temperature, it is preferable to take the measurement when the average temperature of the winding becomes equal to the reference temperature.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.