Relay Protection Basics: Types of Transmission Line Faults and Fundamental Protection Schemes

Leon
Field: Fault Diagnosis
China

1. Types of Faults on Power Lines

Phase-to-Phase Faults:

  • Three-phase short circuit

  • Two-phase short circuit

Ground Faults:

  • Single-phase to ground fault

  • Two-phase to ground fault

  • Three-phase to ground fault

2. Definition of Relay Protection Devices
When an abnormality or fault occurs in a component of a power system, relay protection devices are those that can quickly and selectively isolate the faulty or abnormal component from the system, ensuring the continued normal operation of the remaining healthy equipment.

Examples include: overcurrent protection, distance protection, zero-sequence protection, and high-frequency protection.

  • Main Protection: Protection that meets the basic requirements for system stability and equipment safety during a short-circuit fault. It operates first to trip the circuit breaker and selectively clears faults on the protected equipment or entire line.

  • Backup Protection: Protection that removes the fault if the main protection or circuit breaker fails to operate.

  • Auxiliary Protection: Simple protection added to compensate for limitations in main and backup protection.

3. Role of Relay Protection in Transmission Lines
During operation, transmission lines may experience faults due to strong winds, ice and snow, lightning strikes, external damage, insulation failure, or pollution flashover. In such cases, the relay protection device can act quickly and selectively, tripping the line circuit breaker (switch).

If the fault is transient, the switch successfully recloses after the fault disappears, restoring safe power supply. If the fault is permanent, the reclosing fails, and the faulty line is rapidly isolated, ensuring uninterrupted power supply to the healthy lines.

4. Overcurrent Protection Devices
Overcurrent protection devices are designed based on the significant increase in current during a line fault. When the fault current reaches the protection setting (pickup current), the device initiates operation. Once the time delay setting is reached, the line circuit breaker trips.

Common types include:

  • Instantaneous Overcurrent Protection: Simple, reliable, and fast-acting, but only protects a portion (typically 80–85%) of the same line.

  • Time-Delayed Overcurrent Protection: Operates with a short time delay, protecting the full length of the line and coordinating with the instantaneous protection of the next downstream line.

  • Overcurrent Protection: Set to avoid maximum load current. It protects the entire length of the line and the full length of the next line, serving as backup protection.

  • Directional Overcurrent Protection: Adds a power direction element to overcurrent protection. It operates only when the fault power flows from the bus to the line, preventing misoperation during reverse-direction faults.

5. Distance Protection Devices
Distance protection responds to the impedance (or distance) between the fault point and the protection installation point. It has excellent directional characteristics and is widely used on high-voltage ring networks. Three-stage distance protection is commonly employed:

  • Zone I: Instantaneous operation, protecting 80%–85% of the line length.

  • Zone II: Protects the entire length of the line and extends into part of the next line (typically Zone I of the adjacent line).

  • Zone III: Protects the full length of this line and the next line, serving as backup for Zones I and II.

6. Zero-Sequence Current Protection Devices
In directly grounded neutral systems (also known as high-earth-fault-current systems), a single-phase-to-ground fault produces a significant zero-sequence current. Protection devices that use this current are called zero-sequence current protection devices. A three-stage configuration is commonly used:

  • Stage I: Instantaneous zero-sequence current protection, covering 70%–80% of the line length.

  • Stage II: Time-delayed zero-sequence current protection, covering the full line length and part of the next line.

  • Stage III: Zero-sequence overcurrent protection, covering the full line and serving as backup for the next line.

7. High-Frequency Protection Devices
High-frequency protection converts the phase angle (or power direction) of currents at both ends of a line into high-frequency signals, which are transmitted via a high-frequency channel to the opposite end. The system compares the current phase or power direction at both ends.

This protection only responds to faults within the protected line section and does not require coordination with downstream lines. It operates without time delay, enabling rapid clearance of any fault along the protected line.

Based on operating principles, high-frequency protection is classified into:

  • Blocking Type (Directional Comparison): Compares power direction at both ends.

  • Phase Comparison Type: Compares current phase angles at both ends.

8. Automatic Reclosing Devices
An automatic reclosing device is one that automatically re-closes the circuit breaker after it has tripped.

Function:

  • For transient faults, after the fault clears, the device quickly re-closes the breaker, restoring normal power supply.

  • For permanent faults, the reclosing fails, the breaker trips again, and the faulty line is isolated, ensuring continued power supply to healthy lines.

9. Line Fault Recorder
A device that automatically records the waveforms of current and voltage before and during a line fault, along with the timing and circuit breaker operation status.

By analyzing the recorded waveforms, the fault type can be accurately determined, and the approximate fault location can be calculated. This provides critical data for fault analysis, troubleshooting, and restoration of normal power supply.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
How to Judge, Detect and Troubleshoot Transformer Core Faults
1. Hazards, Causes, and Types of Multi-Point Grounding Faults in Transformer Cores1.1 Hazards of Multi-Point Grounding Faults in the CoreUnder normal operation, a transformer core must be grounded at only one point. During operation, alternating magnetic fields surround the windings. Due to electromagnetic induction, parasitic capacitances exist between the high-voltage and low-voltage windings, between the low-voltage winding and the core, and between the core and the tank. The energized windin
01/27/2026
5 Fault Diagnosis Techniques for Large Power Transformers
Transformer Fault Diagnosis Methods1. Ratio Method for Dissolved Gas AnalysisFor most oil-immersed power transformers, certain combustible gases are produced in the transformer tank under thermal and electrical stress. The combustible gases dissolved in oil can be used to determine the thermal decomposition characteristics of the transformer oil-paper insulation system based on their specific gas content and ratios. This technology was first used for fault diagnosis in oil-immersed transformers.
12/20/2025
Chinese Gas-Insulated Switchgear Enables Commissioning of Longdong-Shandong ±800kV UHV DC Transmission Project
On May 7, China's first large-scale integrated wind-solar-thermal-storage comprehensive energy base UHV transmission project—the Longdong~Shandong ±800kV UHV DC transmission project—was officially energized and put into operation. The project has an annual transmission capacity exceeding 36 billion kilowatt-hours, with new energy sources accounting for more than 50% of the total. After commissioning, it will reduce carbon dioxide emissions by approximately 14.9 million tons annually, contributin
12/13/2025
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.