Does the cable tail protection block autorecloser?

Encyclopedia
Field: Encyclopedia
0
China

The relationship between the tail protection of the cable and the automatic reclosing.

The problem of reclosing in cable line protection

In cable line protection, the application of automatic reclosing has certain limitations. Automatic reclosing is usually used for overhead line transmission and power supply lines as an effective accident prevention measure. However, for cable lines, due to their characteristics, the application of automatic reclosing is not common.

The characteristics of cable lines

The cable line has the following characteristics compared to the overhead line:

  • Less affected by external forces: Cable lines buried underground or laid in cable ducts are less influenced by external environments (such as wind and lightning strikes).

  • Fewer Instantaneous Failures: Due to less influence from external forces, there are relatively few instantaneous failures in cable lines.

  • Mostly permanent faults: Faults in cable lines are mostly permanent faults due to insulation breakdown, such as construction digging and connector burning.

The Challenges of Automatic Reclosing in Cable Lines

Since cable line faults are mostly permanent, the success rate of automatic reclosing is low in these cases. Moreover, reclosing may aggravate the degree of insulation damage, further expanding the impact range of the fault and making the working environment of the circuit breaker more severe, causing another impact on the system.

The function of the cable tail protection

Cable tail protection is mainly a protective measure for the end of the cable, aiming to prevent insulation breakdown and other forms of damage at the end of the cable. This protection usually includes insulation monitoring, overcurrent protection and other means.

The relationship between the tail protection of the cable and the automatic reclosing.

The protection at the tail of the cable does not directly prevent the execution of automatic reclosing. However, since faults in cable lines are mostly permanent, the success rate of automatic reclosing is still low, even with tail protection measures in place. Therefore, in practical engineering, protective measures for cable lines usually do not employ automatic reclosing.

Conclusion

To sum up, the protection at the end of the cable will not directly prevent the execution of automatic reclosing. However, since most faults in cable lines are permanent faults, the success rate of automatic reclosing in such cases is low. Therefore, automatic reclosing is generally not adopted in practical engineering.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.