• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


3.6kV-24kVThe Indoor metal-clad withdrawable switchgear

  • 3.6kV-24kVThe Indoor metal-clad withdrawable switchgear

Key attributes

Brand ROCKWILL
Model NO. 3.6kV-24kVThe Indoor metal-clad withdrawable switchgear
Rated voltage 12kV
Series KYN

Product descriptions from the supplier

Description

Description:

The Indoor metal-clad withdrawable switchgear(hereinafter short as switchgear) is a complete power distribution device for 3.6~40.5kV, 3-phase AC 50/60Hz,single-bus and single-bus sectionalized system.

It is mainly used for power transmission of middle/small generators in power plants; power receiving, transmission for substations in power distribution and power system of factories, mines and enterprises, and starting of large high-voltage motor, etc. so as to control, protect and monitor the system. The medium voltage switchgear meets IEC298,GB3906-91. In addition to be used with domestic VS1 vacuum circuit breaker, it can also be used with VD4 from ABB, 3AH5 from Siemens domestic ZN65A, and VB2 from GE, etc. It is truly a power distribution device with good performance.

In order to meet the requirements for wall mounting and front-end maintenance, the medium voltage switchgear is equipped with a special current transformer, so that the operator can maintain and inspect it in front of the cubicle.

  • Enclosures able to withstand internal arcing.

  • 3 or 4 sides internal arc protection IAC: A-FL and A-FLR. Internal arc withstand: 12.5 kA 1s, 16 kA 1s and 20 kA 1s.

  • Mechanical and electrical interlocks, to prevent incorrect operations.

  • 100% factory-tested without the need for further tests on site.

  • Easy upgraded to meet your need and adapted to the extension of your installations.

  • Integration in factory-built outdoor substations for which the SM6 is particularly well designed.

  • Intelligent, connectable components like SC110 and TH110 provide continuous information about the health of your electrical installations, enabling asset management optimization through preventive maintenance.

Technical parameters:

image.png

Product detail:


企业微信截图_17211091605892.png

企业微信截图_17211092656460.png

企业微信截图_17211092834133.png

What is the working principle of the indoor metal armored pull-out  switchgear?

Circuit Control and Protection:

  • Circuit Control:

  • Circuit breakers control the opening and closing of circuits. The working principle of circuit breakers is based on electromagnetic induction and thermal effects. During normal operation, current flows through the contacts of the circuit breaker, which remain closed. When an overload condition occurs, and the current exceeds the rated current of the circuit breaker, the internal thermal trip mechanism will open the contacts due to the heat generated by the current, thereby interrupting the circuit.

  • In the event of a short circuit, the high short-circuit current will cause the internal electromagnetic trip mechanism to act instantly, quickly opening the contacts and protecting electrical equipment and lines from damage caused by excessive current.

Protection Devices:

  • Other protective devices, such as overcurrent relays and ground fault protection relays, are also equipped. These protection devices continuously monitor parameters such as current and voltage in the circuit. If any abnormality is detected, they send a trip signal to the circuit breaker, ensuring the safety of the circuit.

Power Distribution:

  • Power is introduced into the switchgear's busbar compartment via busbars. The busbars distribute the power to the circuit breakers in each branch. The circuit breakers then transmit the power to different load circuits, enabling the control of power supply to multiple loads. For example, in a building's power distribution system, medium-voltage power from a substation first enters the busbar of the switchgear and is then distributed to the distribution panels on each floor through circuit breakers, providing power to lighting, outlets, and other equipment on those floors.

Interlocking Functions:

  • To ensure operational safety, the switchgear is equipped with various interlocking mechanisms. For example:

  • The trolley can only be moved from the service position to the test or maintenance position when the circuit breaker is in the open (off) state.

  • There is an interlock between the grounding switch and the circuit breaker. When the grounding switch is in the closed (on) position, the circuit breaker cannot be closed, and vice versa.

  • These interlocking devices effectively prevent operator errors and avoid dangerous operations such as switching under load or closing the grounding switch while the circuit is energized.



Know your supplier
Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m²m² Total staff: 700+ Highest Annual Export(usD): 150000000
Workplace: 108000m²m²
Total staff: 700+
Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: High Voltage Electrical Apparatus/Electric transformer
Whole life care manager
Whole-life care management services for equipment procurement, use, maintenance, and after-sales, ensuring safe operation of electrical equipment, continuous control, and worry-free electricity consumption.
The equipment supplier has passed platform qualification certification and technical evaluation, ensuring compliance, professionalism, and reliability from the source.

Related Products

Related Knowledges

  • Main Transformer Accidents and Light Gas Operation Issues
    1. Accident Record (March 19, 2019)At 16:13 on March 19, 2019, the monitoring background reported a light gas action of No. 3 main transformer. In accordance with the Code for Operation of Power Transformers (DL/T572-2010), operation and maintenance (O&M) personnel inspected the on-site condition of No. 3 main transformer.On-site confirmation: The WBH non-electrical protection panel of No. 3 main transformer reported a Phase B light gas action of the transformer body, and the reset was ineff
    02/05/2026
  • Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
    Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
    01/30/2026
  • Neutral point grounding operation mode for 110kV~220kV power grid transformers
    The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
    01/29/2026
  • Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
    Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
    01/29/2026
  • Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
    Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
    01/29/2026
  • Understanding Transformer Neutral Grounding
    I. What is a Neutral Point?In transformers and generators, the neutral point is a specific point in the winding where the absolute voltage between this point and each external terminal is equal. In the diagram below, pointOrepresents the neutral point.II. Why Does the Neutral Point Need Grounding?The electrical connection method between the neutral point and earth in a three-phase AC power system is called theneutral grounding method. This grounding method directly affects:The safety, reliabilit
    01/29/2026

Related Solutions

  • Intelligent Operation Solution for 12kV Vacuum Circuit Breakers: Integrating Real-time Monitoring & Lifetime Optimization
    Ⅰ. Equipment Operation & MaintenanceIntelligent Monitoring System Integration​Multi-parameter Real-time Monitoring: Embedded sensors (temperature, displacement, Hall effect current sensors) track contact temperature rise, mechanical characteristics (opening/closing speed, overtravel), coil current, and partial discharge signals. Data undergoes preprocessing via edge computing prior to cloud upload.​Lifetime Prediction Model: Dynamically evaluates remaining lifespan using electrical wear data
    06/10/2025
  • SF6 Circuit Breaker Solutions for Outdoor Installation (Anti-Pollution & Seismic Resistance)
    I.Core Challenges in Outdoor Installation​In high-voltage transmission and distribution systems, SF6 circuit breakers are exposed to complex outdoor environments for extended periods, facing the following critical issues:​Pollution & Insulation Degradation​Dust, salt fog, and industrial pollutants in outdoor environments easily adhere to equipment surfaces. In coastal or industrial areas, pollution levels may reach ​Class IV, resulting in insufficient creepage distance and triggering ​flasho
    05/12/2025
  • 12kV Indoor Vacuum Circuit Breaker Southeast Asia Solution: Anti-Corrosion Compact Design
    12kV Indoor Vacuum Circuit Breaker Southeast Asia Solution: Anti-Corrosion Compact DesignⅠ. Executive Summary​Southeast Asia faces rapidly growing electricity demand alongside environmental challenges including high temperatures, humidity, salt spray corrosion, and grid instability. This solution recommends ​Solid Insulated Pole-Mounted Vacuum Circuit Breakers (VCB)​​ featuring ​high reliability, ​compact design, and ​smart monitoring. Tailored for tropical climates and industrial scenarios, it
    06/10/2025
Haven't found the right supplier yet? Let matching verified suppliers find you. Get Quotation Now
Haven't found the right supplier yet? Let matching verified suppliers find you.
Get Quotation Now
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.