What is the voltage difference between two legs of a two-phase system?

Encyclopedia
10/05/2024

When discussing voltage differences in two-phase systems and between each pole and the ground in a grounded neutral system, we need to clarify some basic concepts.


Two-phase system


Two-phase systems are not common in modern power systems, but have been used at certain times in history. Two-phase systems usually come in two forms: four-wire and two-wire.


Four-wire two-phase system


In this system, the two sets of coils are 90 degrees out of phase and there are two neutral lines connected together. The voltage difference between the two phases (i.e. the voltage between the two poles) is usually the same as the voltage per phase, assuming that the voltage per phase is Vphase, then the voltage difference between the two phases is Vline=Vphase.


Two-wire two-phase system


In such a system, there is no neutral line and the voltage difference between the two phases is called Vline.


Grounded neutral system


A neutral point system is one in which the neutral line in the system is grounded, which is the most common configuration in three-phase systems, but is also applicable in two-phase systems.


The voltage difference of a grounded neutral system


In a neutral point system at a contact, the voltage between each pole and the ground depends on the configuration and load of the system. If the system is balanced and the neutral point is grounded, the voltage between each pole and the ground should be half of the Vphase, because ideally the neutral point should have a potential of 0V.


However, in practical applications, due to load imbalance or other factors, the neutral point may drift, resulting in the voltage between each pole and the ground not being completely consistent.


Illustrate by example


Suppose that in a connected neutral point system, the voltage of each phase is Vphase, then:


  • The voltage difference between the two phases (if a four-wire system) is Vline=Vphase.



  • The voltage between each pole and the ground is ideally Vphase/2.


Precautions in practical application


In practical applications, the following situations may be encountered:


  • Load imbalance: If the load is not perfectly symmetrical, the neutral points may drift, resulting in a different voltage between each pole and the ground.


  • System design: The specific design and configuration of the system also affects the voltage between each pole and the ground.


Sum up


  • Two-phase system: The voltage difference between the two phases depends on the specific configuration of the system, generally V phase or Vline.


  • Grounded neutral system: The voltage between each pole and the ground is usually V phase/2, but may vary in practice due to factors such as load imbalance.



In the specific application, it is recommended to refer to the specific design parameters of the system and the actual situation to determine the voltage difference. If there are specific system parameters, a more precise answer can be provided.


Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

Working Voltage in Power System
Working Voltage in Power System
Working VoltageThe term "working voltage" refers to the maximum voltage that a device can withstand without sustaining damage or burning out, while ensuring the reliability, safety, and proper operation of both the device and associated circuits.For long-distance power transmission, the use of high voltage is advantageous. In AC systems, maintaining a load power factor as close to unity as possible is also economically necessary. Practically, heavy currents are more challenging to handle than hi
Encyclopedia
07/26/2025
Frequency division method for measuring grid-to-ground insulation parameters
Frequency division method for measuring grid-to-ground insulation parameters
The frequency division method enables the measurement of grid-to-ground parameters by injecting a current signal of a different frequency into the open delta side of the potential transformer (PT).This method is applicable to ungrounded systems; however, when measuring the grid-to-ground parameters of a system where the neutral point is grounded via an arc suppression coil, the arc suppression coil must be disconnected from operation beforehand. Its measurement principle is shown in Figure 1.As
Leon
07/25/2025
The insulation parameters of the power grid to ground are measured by the tuning method
The insulation parameters of the power grid to ground are measured by the tuning method
The tuning method is suitable for measuring the ground parameters of systems where the neutral point is grounded via an arc suppression coil, but not applicable to ungrounded neutral point systems. Its measurement principle involves injecting a current signal with continuously varying frequency from the secondary side of the Potential Transformer (PT), measuring the returned voltage signal, and identifying the system's resonant frequency.During the frequency sweeping process, each injected heter
Leon
07/25/2025
Effect of Transition Resistance at the Grounding Point on the Rising Speed of Zero - sequence Voltage
Effect of Transition Resistance at the Grounding Point on the Rising Speed of Zero - sequence Voltage
In an arc - suppression coil grounding system, the rising speed of the zero - sequence voltage is greatly affected by the value of the transition resistance at the grounding point. The larger the transition resistance at the grounding point, the slower the rising speed of the zero - sequence voltage.In an ungrounded system, the transition resistance at the grounding point has basically no impact on the rising speed of the zero - sequence voltage.Simulation Analysis: Arc - suppression Coil Ground
Leon
07/24/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!