How do I calculate the fault current at the secondary side of a transformer which is supplying a transmission line with a certain impedance?

Encyclopedia
Field: Encyclopedia
0
China

Calculating the fault current (short-circuit current) on the secondary side of a transformer supplying a transmission line is a complex process that involves multiple parameters of the power system. Below are the steps and relevant formulas to help you understand how to perform this calculation. We will assume the system is a three-phase AC system, and the fault occurs on the transformer's secondary side.

1. Determine System Parameters

Transformer Parameters:

  • Rated capacity of the transformer rated S rated (unit: MVA)

  • Transformer impedance ZT (usually given as a percentage, e.g., ZT =6%)

  • Primary-side voltage of the transformer V1(unit: kV)

  • Secondary-side voltage of the transformer V2 (unit: kV)

Transmission Line Parameters:

  • Impedance of the transmission line ZL (unit: ohms or ohms per kilometer)

  • Length of the transmission line L (unit: kilometers)

Equivalent Source Impedance:

The equivalent impedance of the source ZS (unit: ohms), typically provided by the upstream grid. If the source is very strong (e.g., from a large power plant or infinite bus), you can assume ZS ≈0.

2. Normalize All Impedances to the Same Base

To simplify calculations, it's common to normalize all impedances to the same base value (usually the primary or secondary side of the transformer). Here, we choose to normalize all impedances to the secondary side of the transformer.

  • Base Voltage: Select the secondary-side voltage V2 as the base voltage.

  • Base Capacity: Choose the rated capacity of the transformer rated Srated as the base capacity.

The base impedance is calculated as:

a303e058419e33105d4165227b2802e1.jpeg

where V2  is the secondary-side line voltage (kV), and S rated is the rated capacity of the transformer (MVA).

3. Calculate Transformer Impedance

The transformer impedance ZT is usually given as a percentage and needs to be converted to an actual impedance value. The conversion formula is:

cc18e313a996bc5764173344f4744262.jpeg

4. Calculate Transmission Line Impedance

If the transmission line impedance is given in ohms per kilometer, calculate the total impedance based on the line length L:

94a638355d5c20d8da8668249f38517e.jpeg

5. Calculate Equivalent Source Impedance

If the equivalent source impedance ZS is known, use it directly. If the source is very strong, you can assume ZS≈0.

6. Calculate Total Impedance

The total impedance Ztotal  is the sum of the transformer impedance, transmission line impedance, and equivalent source impedance:

d2206b2e94a08987069742aeda344bc6.jpeg

7. Calculate Fault Current

The fault current Ifault can be calculated using Ohm's Law:

00fd0dfb7dc686a10c67a75c828fc275.jpeg

where V2  is the secondary-side line voltage (kV), and Ztotal  is the total impedance (ohms).

Note: The calculated I fault is the line current (kA). If you need the phase current, divide by 

06a8ba97c2cff4c61eb745afebfe91d0.jpeg

8. Consider System Short-Circuit Capacity

In some cases, it may be necessary to consider the system's short-circuit capacity SC , which can be calculated as:

70cd8a200d7fef9c86e9bb7fe21c6ff2.jpeg

where SC is in MVA.

9. Consider Parallel Transmission Lines

If there are multiple parallel transmission lines, the impedance of each line ZL must be combined in parallel. For n parallel lines, the total transmission line impedance is:

e20db109c9869cca63e720f1a2110e08.jpeg

10. Consider Other Factors

Load Impact: In real systems, loads can affect the short-circuit current, but in most cases, load impedance is much larger than the source impedance and can be neglected.

Relay Protection Action Time: The duration of the short-circuit current depends on the action time of relay protection devices, which typically operate within milliseconds to seconds to clear the fault.

Summary

To calculate the fault current on the secondary side of a transformer supplying a transmission line, you need to consider the transformer impedance, transmission line impedance, and equivalent source impedance. By normalizing all impedances to the same base value and applying Ohm's Law, you can calculate the fault current. In practical applications, you should also consider the action time of relay protection devices and the impact of loads.

Give a tip and encourage the author!
Recommended
How to Maintain a PV Plant? State Grid Answers 8 Common O&M Questions(2)
1. On a scorching sunny day, do damaged vulnerable components need to be replaced immediately?Immediate replacement is not recommended. If replacement is necessary, it is advisable to do so in the early morning or late afternoon. You should contact the power station’s operation and maintenance (O&M) personnel promptly, and have professional staff go to the site for replacement.2. To prevent photovoltaic (PV) modules from being hit by heavy objects, can wire mesh protective screens be install
Encyclopedia
09/06/2025
How to Maintain a PV Plant? State Grid Answers 8 Common O&M Questions(1)
1. What are the common faults of distributed photovoltaic (PV) power generation systems? What typical problems may occur in various components of the system?Common faults include inverters failing to operate or start due to voltage not reaching the startup set value, and low power generation caused by issues with PV modules or inverters. Typical problems that may occur in system components are burnout of junction boxes and local burnout of PV modules.2. How to handle common faults of distributed
Leon
09/06/2025
Short Circuit vs. Overload: Understanding the Differences and How to Protect Your Power System
One of the main differences between a short circuit and an overload is that a short circuit occurs due to a fault between conductors (line-to-line) or between a conductor and earth (line-to-ground), whereas an overload refers to a situation where equipment draws more current than its rated capacity from the power supply.Other key differences between the two are explained in the comparison chart below.The term "overload" typically refers to a condition in a circuit or connected device. A circuit
Edwiin
08/28/2025
Leading vs Lagging Power Factor | Phase Difference Explained
Leading and lagging power factors are two key concepts related to the power factor in AC electrical systems. The main difference lies in the phase relationship between current and voltage: in a leading power factor, the current leads the voltage, whereas in a lagging power factor, the current lags behind the voltage. This behavior depends on the nature of the load in the circuit.What is Power Factor?Power factor is a crucial, dimensionless parameter in AC electrical systems, applicable to both s
Edwiin
08/26/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.