What aspects does the inspection of industrial and commercial energy storage cover?

Oliver Watts
Oliver Watts
Field: Inspection and testing
China

As a frontline tester, I work with industrial and commercial energy storage systems daily. I know firsthand how critical their stable operation is for energy efficiency and business profitability. While installed capacity grows rapidly, equipment failures increasingly threaten ROI—over 57% of energy storage plants reported unplanned outages in 2023, with 80% stemming from equipment defects, system anomalies, or poor integration. Below, I share practical testing insights for the five core subsystems (battery, BMS, PCS, thermal management, EMS) and three - tiered inspection framework (daily checks, periodic maintenance, deep diagnostics) to help fellow practitioners.

1. Core Subsystem Testing Practices
1.1 Battery System: The "Heart" of Energy Storage

Batteries are the energy backbone, requiring comprehensive testing across three dimensions:

(1) Electrochemical Performance Testing

  • Capacity Testing: Follow GB/T 34131—discharge at 0.2C to cutoff voltage (25±2℃), compare actual vs. rated capacity to assess “endurance.”

  • Internal Resistance Testing: Use AC injection (1kHz sine wave, most representative but prone to interference), AC discharge conductance, or DC discharge methods. I recommend enhancing AC injection with Kalman filtering to reduce noise for accuracy.

  • SOC/SOH Monitoring: Combine ampere - hour integration, open - circuit voltage, and electrochemical impedance spectroscopy. Modified ampere - hour integration (accounting for temperature and charge - discharge states) keeps SOC errors <1%.

(2) Safety Performance Testing

  • Thermal Runaway Testing: Follow UL 9540A&mdash;test at cell, module, and system levels to characterize thermal runaway behavior and gas combustion properties (critical for hazard assessment).

  • Overcharge/Overdischarge Testing: Simulate extreme conditions per GB/T 36276 to verify safety thresholds.

  • Short - Circuit Protection Testing: Directly simulate external shorts to validate protective responses (a must - have for system safety).

(3) Physical Condition Testing

  • Visual Inspection: Check for case deformation, leaks, and legible labeling (small details hide big risks).

  • Connector Testing: Inspect for oxidation, corrosion, or looseness; measure contact resistance (poor connections cause operational failures).

  • Ingress Protection (IP) Testing: Follow GB/T 4208 to ensure reliability in harsh environments (dust, moisture, etc.).

1.2 BMS: The "Brain" of Battery Management

BMS monitors and protects batteries&mdash;focus on communication, state estimation, and protection:

(1) Communication Protocol Compatibility Testing

BMS must integrate with PCS/EMS via protocols like Modbus/IEC 61850. Use CAN analyzers (e.g., Vector CANoe) and protocol converters to test:

  • Latency: &le;200ms

  • Success Rate: &ge;99%

  • Data Integrity: No loss/corruptio.

I use finite - state machine (FSM) - based test case generation to cover all communication scenarios.

(2) SOC/SOH Algorithm Validation

Ensure SOC errors &le;&plusmn;1% and SOH errors &le;&plusmn;5% (GB/T 34131):

  • Offline Calibration: Compare BMS estimates to lab - measured capacity / Internal Resistance

  • Online Testing: Simulate real - world charge - discharge cycles.

  • Battery simulators and BMS interface emulators automate this for efficiency.

(3) Cell Balancing Testing

  • Active Balancing: Simulate cell mismatches to validate BMS strategies.

  • Passive Balancing: Track long - term mismatch trends.
    Use results to judge if balancing meets system needs.

(4) Safety Protection Testing

Trigger overcharge, overdischarge, and thermal protection:

  • Example: Overcharge test&mdash;continue charging a full battery to verify BMS disconnects the circuit.
    Must meet GB/T 34131 requirements.

1.3 PCS: The "Power Hub" for Energy Conversion

PCS converts AC/DC&mdash;test efficiency, protection, and power quality:

(1) Efficiency Testing

Meet GB/T 34120 (&ge;95% efficiency at rated power):

  • Input - Output Comparison: Measure power at both ends to calculate efficiency.

  • Load Profiling: Test across loads to map efficiency curves.
    Use high - precision analyzers (e.g., Fluke 438 - II) at 25&plusmn;2℃ for accuracy.

(2) Protection Testing

Validate overload (110% rated load), short - circuit, and overvoltage responses. Must meet GB/T 34120.

(3) Harmonic Analysis

Ensure THD &le;5% (GB/T 14549/GB/T 19939):

  • Direct Measurement: Use power quality analyzers (e.g., Fluke 438 - II) to test waveforms.

  • FFT Analysis: Calculate harmonic amplitudes from current signals.

  • Test across loads and operating conditions.

(4) Output Stability Testing

Measure voltage, frequency, and power factor stability under varying loads. Use high - precision scopes/analyzers to verify compliance.

1.4 Thermal Management System: The "Cooling Guardian"

Maintains optimal battery temperature&mdash;test cooling, temperature control, and ruggedness:

(1) Cooling Performance Testing

  • Air - Cooled Systems: Test filter clogging (pressure drop) and fan life (vibration analysis).

  • Liquid - Cooled Systems: Test pipeline pressure (hydraulic sensors) and coolant flow (flowmeters).
    Must meet GB/T 40090. Example: CATL uses modified K - means clustering + wavelet denoising to predict SOH with <3% error.

(2) Temperature Control Precision Testing

  • Uniformity: Deploy sensors across the battery pack, ensure max &Delta;T &le;5℃ (GB/T 40090; liquid - cooled systems target &le;2℃).

  • Response Time: Measure time to stabilize temperature after environmental changes.

(3) Ruggedness Testing

Conduct IP (GB/T 4208), vibration (GB/T 4857.3), and salt - spray (GB/T 2423.17) tests. Critical for extreme environments (e.g., Huawei&rsquo;s Red Sea project uses distributed cooling for 50℃ conditions).

(4) Leak Detection (Liquid - Cooled Only)

  • Fluorescent Tracer: Add dye, inspect with UV light.

  • Pressure Testing: Pressurize lines to check seals.

  • Ensure no leaks and stable coolant pressure.

1.5 EMS: The "Commander" of Energy Management

Optimizes operation and dispatching&mdash;test algorithms, communication, and security:

(1) Algorithm Accuracy Testing

Validate load forecasting, charge - discharge optimization, and economics:

  • Historical Backtesting: Use past data to verify models.

  • Live Testing: Validate with real - time operations.

  • Example: CATL&rsquo;s AI cuts fault detection time by 7 days, boosting efficiency by 3% and reducing losses by 25%.

(2) Communication Protocol Compatibility Testing

Ensure support for IEC 61850/Modbus (IEC 62933 - 5 - 2):

  • Conformance Testing: Verify compliance with standards.

  • Interoperability Testing: Test integration with BMS/PCS.

(3) Data Security Testing

Validate SM4 encryption, access control, and integrity (per national crypto standards):

  • Encryption: Test SM4 key exchange.

  • Access Control: Verify user permission enforcement.

  • Integrity: Ensure no data loss/corruption during transit/storage.

(4) Response Time Testing

Ensure system response &le;200ms (GB/T 40090) to handle grid demands. Trigger EMS actions and measure latency.

2. Three - Tiered Inspection Framework
2.1 Daily Checks (Rapid Fault Detection)

Conducted per shift to catch issues early:

  • Scope: Battery temp/voltage/SOC, BMS communication, PCS parameters, thermal cooling, EMS data.

  • Tools: Thermal cameras, multimeters, oscilloscopes, communication testers.

  • Focus: System status and anomalies&mdash;address issues immediately.

2.2 Periodic Maintenance (Preventive Care)

Scheduled to extend lifespan:

  • Scope: Battery internal resistance (AC injection), BMS firmware updates/SOC calibration, PCS efficiency/harmonics, thermal system seals/IP, EMS algorithm updates/security checks.

  • Tools: Dedicated resistance meters, CAN analyzers, power analyzers, encryption tools.

  • Cadence: Tailor to equipment (e.g., quarterly battery tests, semi - annual BMS updates).

2.3 Deep Diagnostics (Root - Cause Analysis)

Triggered by recurring issues (e.g., frequent thermal runaway alerts, BMS communication failures):

  • Scope: Thermal runaway (UL 9540A), BMS fault diagnosis, PCS protection/efficiency deep dives, thermal system leak/vibration tests, EMS algorithm validation/security scans.

  • Tools: Thermal runaway chambers, vibration analyzers, encryption scanners, fault injectors.

  • Goal: Identify root causes for targeted repairs/upgrades.

3. Best Practices: Standardization, Data - Driven Testing, Prevention
3.1 Standardization

Follow IEC 62933 - 5 - 2/GB/T 40090 - 2021:

  • Process: Define preparation (scope, tools, environment), execution (testing + data logging), and analysis (reporting).

  • Reports: Include equipment specs, test conditions, data, results, and recommendations (per GB/T 40090 requirements for traceability).

3.2 Data - Driven Testing

Build a unified data pipeline (battery temp, voltage, SOC, PCS efficiency, THD, etc.). Use AI (LSTM, random forests) and digital twins:

  • Example: CATL&rsquo;s AI predicts SOC errors <1% and SOH decay with >95% accuracy, issuing 7 - day advance thermal runaway alerts.

  • Example: Huawei uses digital twins to simulate extreme conditions, pre - identifying failures.

3.3 Preventive Testing

Schedule proactive checks based on equipment behavior:Cadence: Quarterly cell balancing, semi - annual BMS updates, annual PCS harmonics/thermal seals checks, quarterly EMS algorithm updates.

  • Triggers: Deep diagnostics for &ge;5% internal resistance rise (3 consecutive tests) or recurring communication failures.

Frontline testing demands rigor, expertise, and practical know - how. Mastering these subsystems, tools, and strategies ensures energy storage systems deliver reliability and efficiency&mdash;safeguarding business and grid operations. This guide distills years of hands - on experience&mdash;I hope it empowers fellow testers to raise the bar in energy storage reliability.

Give a tip and encourage the author!
Recommended
How to Test Vacuum in Vacuum Circuit Breakers
How to Test Vacuum in Vacuum Circuit Breakers
Vacuum Integrity Testing of Circuit Breakers: A Critical Measure for Performance EvaluationVacuum integrity testing is a key method for assessing the vacuum performance of circuit breakers. This test effectively evaluates the insulation and arc-quenching capabilities of the breaker.Before testing, ensure the circuit breaker is properly installed and correctly connected. Common vacuum measurement methods include the high-frequency method and the magnetic control discharge method. The high-frequen
Oliver Watts
10/16/2025
Ensure Hybrid System Reliability with Full Production Testing
Ensure Hybrid System Reliability with Full Production Testing
Production Testing Procedures and Methods for Wind-Solar Hybrid SystemsTo ensure the reliability and quality of wind-solar hybrid systems, several critical tests must be conducted during production. Wind turbine testing primarily includes output characteristic testing, electrical safety testing, and environmental adaptability testing. Output characteristic testing requires measuring voltage, current, and power under varying wind speeds, plotting wind-power curves, and calculating power generatio
Oliver Watts
10/15/2025
Electrical Meter Accuracy Issues? Solutions Revealed
Electrical Meter Accuracy Issues? Solutions Revealed
Analysis of Measurement Errors in Electrical Instruments and Elimination Strategies1.Electrical Instruments and Common Testing MethodsElectrical instruments play a vital role in the generation, transmission, and utilization of electricity. As a special form of energy, electricity requires strict safety standards in production and use. Safe electricity usage is crucial to daily life, production, and socio-economic development. Power system monitoring relies on electrical instruments, which are of
Oliver Watts
10/07/2025
High-Voltage Electrical Testing: Key Safety Requirements for Field Operations
High-Voltage Electrical Testing: Key Safety Requirements for Field Operations
The test site layout must be reasonable and organized. High-voltage testing equipment should be placed close to the test object, live parts must be isolated from each other, and remain within the clear line of sight of test personnel. Operational procedures must be rigorous and systematic. Unless otherwise specified, voltage must not be suddenly applied or removed during operation. In case of abnormal conditions, voltage increase must be stopped immediately, pressure rapidly reduced, power disc