Are PM Actuators Reliable? Compare Types & Benefits

Edwiin
Edwiin
Field: Power switch
China

The performance of circuit breaker operating mechanisms is decisive for reliable and safe power supply. While various mechanisms each have their advantages, the emergence of a new type does not completely replace traditional ones. For example, despite the rise of eco-friendly gas insulation, solid insulation ring main units still hold about 8% of the market, showing new technologies rarely fully displace existing solutions.

The permanent magnet actuator (PMA) consists of permanent magnets, a closing coil, and an opening coil. It eliminates mechanical linkages, tripping and latching mechanisms found in spring-operated mechanisms, resulting in a simple structure with very few parts. Only one primary moving component operates during switching, providing high reliability. It uses permanent magnets to maintain the breaker’s position, belonging to the category of electromagnetic actuation with permanent magnetic latching and electronic control. However, due to the high electromagnetic energy required for closing and opening, a large-capacity energy storage capacitor is typically needed.

ABB.jpg

PMA mechanisms are classified into different types, mainly single-stable and bi-stable, and single-coil or dual-coil configurations, with no clear superiority among them.

A bi-stable permanent magnet mechanism uses permanent magnets at both the closing and opening positions for latching. Closing and opening actions are achieved by energizing separate excitation coils to drive the moving iron core. Under the same conditions, the bi-stable type has a lower peak closing current. Smaller currents simplify control circuitry, enhance reliability, and reduce the risk of controller damage. Additionally, smaller capacitor capacity is required—typically a 100V/100,000μF electrolytic capacitor can support reclosing operations. However, the initial opening speed of a bi-stable PMA vacuum circuit breaker is lower than its average speed over full contact travel.

A single-stable permanent magnet mechanism uses a permanent magnet for closing position latching, while a spring maintains the open position. Closing is achieved by energizing the closing coil to drive the moving core, simultaneously storing energy in the opening spring. Opening is accomplished by releasing the stored energy in the spring.

Since the single-stable PMA relies on a spring for opening, its initial opening speed and average opening speed are superior to those of the bi-stable type, better matching the breaker’s opening counter-force characteristics. However, because energy must be stored in the opening spring during closing, the peak closing current is significantly higher than in a bi-stable mechanism under comparable conditions.

The AMVAC permanent magnet actuated vacuum circuit breaker has a maximum rated voltage of 27kV. The 15kV model supports a rated current up to 3000A, a short-circuit breaking current of 50kA, and a short-circuit making current of 130kA.

Why Hasn't It Been Widely Adopted?

1. Cost-Effectiveness (Value for Money)

PMA circuit breakers have fewer moving parts, a simpler structure, and electromagnetic force characteristics well-matched to vacuum interrupters. They offer mechanical endurance exceeding 100,000 operations—significantly higher than the 30,000 operations typical of spring mechanisms. This makes them ideal for frequent switching and high-operation-count applications. Their electronic control also facilitates automation. However, high-quality PMA breakers are significantly more expensive. As a result, they are primarily used in premium applications abroad, such as in petrochemical plants and offshore platforms, where maintenance-free operation, high reliability, and improved power continuity are critical.

2. Quality Concerns

PMA breakers demand extremely high-quality components, including capacitors, permanent magnets, electromagnets, and electronic circuits. Comparing low-end PMA breakers with standard spring mechanisms is unfair and misleading. Using inferior capacitors or other components compromises overall product quality. Unlike spring-operated mechanisms, which allow individual component replacement and repair, PMA mechanisms are difficult and costly to repair. This high replacement cost further hinders the widespread adoption of PMA circuit breakers.

Give a tip and encourage the author!
Recommended
Complete Guide to Circuit Breaker Selection and Setting Calculation
Complete Guide to Circuit Breaker Selection and Setting Calculation
How to Select and Set Circuit Breakers1. Types of Circuit Breakers1.1 Air Circuit Breaker (ACB)Also known as a molded frame or universal circuit breaker, all components are mounted within an insulated metal frame. It is typically open-type, allowing easy replacement of contacts and parts, and can be equipped with various accessories. ACBs are commonly used as main power supply switches. Overcurrent trip units include electromagnetic, electronic, and intelligent types. They provide four-stage pro
Echo
10/28/2025
What are the common issues in SF₆ gas circuit faults and circuit breaker failure-to-operate faults?
What are the common issues in SF₆ gas circuit faults and circuit breaker failure-to-operate faults?
This article categorizes faults into two main types: SF₆ gas circuit faults and circuit breaker failure-to-operate faults. Each is described below:1.SF₆ Gas Circuit Faults1.1 Fault Type: Low gas pressure, but density relay does not trigger alarm or lockout signalCause: Faulty density gauge (i.e., contact not closing)Inspection & Handling: Calibrate actual pressure using a standard gauge. If confirmed, replace the density gauge.1.2 Density Relay Triggers Alarm or Lockout Signal (but pressure
Felix Spark
10/24/2025
Vacuum Circuit Breaker Withstand Voltage Test Guide
Vacuum Circuit Breaker Withstand Voltage Test Guide
Insulation Withstand Voltage Test Standards for Vacuum Circuit BreakersThe main purpose of the insulation withstand voltage test for vacuum circuit breakers is to verify whether the insulation performance of the equipment under high voltage is qualified, and to prevent breakdown or flashover accidents during operation. The test process must be strictly carried out in accordance with power industry standards to ensure equipment safety and power supply reliability.Test ObjectsThe test objects incl
Garca
10/18/2025
Vacuum Circuit Breaker Loop Resistance Standards
Vacuum Circuit Breaker Loop Resistance Standards
Standard for Loop Resistance of Vacuum Circuit BreakersThe standard for loop resistance of vacuum circuit breakers specifies the required limits for the resistance value in the main current path. During operation, the magnitude of loop resistance directly affects the safety, reliability, and thermal performance of the equipment, making this standard critically important.Below is a detailed overview of the loop resistance standard for vacuum circuit breakers.1. Significance of Loop ResistanceLoop