• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What are the troubleshooting methods for current transformers?

Felix Spark
Felix Spark
Field: Failure and maintenance
China

As a front - line fault maintenance worker, I deal with current transformers (CTs) daily. A CT’s secondary winding in operation must never open - circuit! Once open - circuited, the secondary current and demagnetizing potential vanish. All primary - side magnetic potential then becomes the iron core’s exciting potential, sharply increasing its magnetic flux density. High voltage on the secondary side will endanger safety anytime.

Despite strict power operation regulations, user electricians have poor management and technical quality. Since the power operation market opened, design units often fail to design to specs, and installation teams don’t follow drawings or safety measures. Thus, CT accidents during operation keep rising. A typical capacity - increase project accident I recently handled illustrates this, and I’ll share it.

1. Fault Discovery: The Scene of a Burnt - out Transformer

On September 27, 2012, our engineering installation company took on a substation capacity - increase project. When we cut off the power to replace the CT in the incoming line cabinet, I removed it and found that — the CT was burned beyond recognition! Having been in maintenance for so many years, I've seen many burnt - out ones, but a CT suddenly burning out must be fishy, and we must dig deep into the reasons.

2. Cause Analysis: Man - made Open Circuit + Management Chaos
(1) On - site Investigation, Locking on "Secondary Wires Cut"

My team and I conducted a thorough investigation: The secondary outgoing wires of the CT in the incoming line cabinet were actually cut off! Tracing back, it turned out that this matter dated back to the commissioning of the substation:

  • Initially, the transformation ratios of the incoming line cabinet and the metering cabinet were both 75/5;

  • During the first capacity increase, the CT of the metering cabinet was replaced with one with a transformation ratio of 150/5, but the CT for protection in the incoming line cabinet was not replaced and remained 75/5;

  • After the capacity increase, the equipment showed no abnormalities, but as the transformer capacity increased, the protection setting value was not adjusted accordingly.

(2) Misjudging the Fault, Man - made Open Circuit

Later, as the electricity consumption increased, the over - current protection tripped frequently. The user electrician couldn't find the problem and mistakenly thought it was a CT fault causing the relay to operate, and actually cut off the secondary wires! After power transmission, the protection didn't trip, but the secondary circuit of the CT was directly open - circuited — this was a disaster!

(3) Hazards of Open Circuit: Iron Core Saturation → Burning

The secondary side of the CT originally has a small impedance and operates close to a short - circuit. Once open - circuited, the magnetic force generated by the primary current cannot be offset by the secondary side, the iron core is severely saturated, the iron loss increases sharply, and the CT itself overheats and burns out directly.

In the final analysis, this incident was a major management loophole: The construction team failed to replace the CT in the incoming line cabinet, the protection setting value was not updated, and the electrician operated blindly, leading to the CT being damaged layer by layer.

3. Preventive Measures: A "Life - saving Checklist" for Maintenance Workers

In our line of work, we must plug the loopholes from the source. Combining this accident, I have sorted out 6 strict measures, and operation and maintenance, design, and installation must all follow the rules:

(1) Design + Drawing Review: Strictly Comply with Specifications

Design units must conduct on - site surveys and produce drawings in accordance with specifications; the owner must supervise the drawing review to prevent "wrong designs" from entering the site.

(2) Equipment Control: Full - process Supervision

The owner must follow national and industry standards for procurement, testing, and acceptance to prevent defective products from entering the power grid.

(3) Operation Qualifications: Electricians Must Be Certified

If operation and maintenance personnel have no qualifications? Don't let them touch the equipment! Moreover, random modification of wiring and disassembly of equipment are strictly prohibited — this is a red line.

(4) Installation and Acceptance: Keep an Eye on the Construction Team

The installation team must follow the procedures, and any wrong installation, corner - cutting, or under - installation must be reworked immediately! The acceptance must be strict to avoid hidden dangers.

(5) Regular Inspections: Strengthen in Special Periods

Daily inspections and panel monitoring are essential, and special periods such as high load, high temperature, and typhoon days must be closely monitored! Check the appearance, smell for peculiar odors, and listen for abnormal noises to detect abnormalities early.

(6) Overhaul and Testing: Don't Let "Sick CTs" Be Put into Use

Overhauls must be carried out in strict accordance with standards, and the process must be in place; electrical tests must be thorough, and CTs with defects must never be put into use.

4. Conclusion: CT Open Circuit is Extremely Dangerous, Maintenance Workers Must Know "Prevention and Rescue"

A secondary open - circuit of a CT is no small matter; it can cause equipment outages, protection maloperations/refusals to operate, and lead to major accidents at any time. As front - line maintenance workers, we must thoroughly understand the hazards and causes of open circuits, conduct more inspections and investigations in daily work, and be able to solve problems immediately when abnormalities occur. Only by implementing these measures can CTs operate stably and the power grid have fewer troubles!

Give a tip and encourage the author!
Recommended
Harmonic THD Impact: From Grid to Equipment
Harmonic THD Impact: From Grid to Equipment
The impact of harmonic THD errors on power systems must be analyzed from two aspects: "actual grid THD exceeding limits (excessive harmonic content)" and "THD measurement errors (inaccurate monitoring)" — the former directly damages system equipment and stability, while the latter leads to improper mitigation due to "false or missed alarms." When combined, these two factors amplify system risks. The impacts span the entire power chain — generation → transmission → distribution → consumption — af
Edwiin
11/01/2025
Hydraulic Leak & SF6 Gas Leakage in Circuit Breakers
Hydraulic Leak & SF6 Gas Leakage in Circuit Breakers
Leakage in Hydraulic Operating MechanismsFor hydraulic mechanisms, leakage can cause short-term frequent pump starting or excessively long re-pressurization time. Severe internal oil seepage in valves may lead to pressure loss failure. If hydraulic oil enters the nitrogen side of the accumulator cylinder, it can cause abnormal pressure rise, which affects the safe operation of SF6 circuit breakers.Apart from failures caused by damaged or abnormal pressure detection devices and pressure component
Felix Spark
10/25/2025
How Acoustic Imaging Locates GIS Defects
How Acoustic Imaging Locates GIS Defects
In recent years, acoustic imaging technology for GIS defect detection has developed rapidly. This technology enables intuitive sound source localization, helping operation and maintenance personnel focus on the exact location of GIS defects, thereby improving the efficiency of defect analysis and resolution.Sound source localization is only the first step. It would be even more ideal if common GIS defect types could be automatically identified using artificial intelligence (AI), along with intel
Edwiin
10/24/2025
Why Can't VT Be Shorted & CT Be Opened? Explained
Why Can't VT Be Shorted & CT Be Opened? Explained
We all know that a voltage transformer (VT) must never operate short-circuited, while a current transformer (CT) must never operate open-circuited. Short-circuiting a VT or opening the circuit of a CT will damage the transformer or create hazardous conditions.From a theoretical standpoint, both VTs and CTs are transformers; the difference lies in the parameters they are designed to measure. So why, despite being fundamentally the same type of device, is one prohibited from short-circuit operatio
Echo
10/22/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.