• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Network distribution transformers serving grid and spot networks

Echo
Field: Transformer Analysis
China

Housed in Vaults
Network transformers, which are distribution transformers serving grid and spot networks, are large - sized three - phase units.

According to ANSI C57.12.40 - 1982, network units are typically categorized as vault - type or subway - type:
  • Vault - type transformers: Suitable for occasional submerged operation.
  • Subway - type transformers: Suitable for frequent or continuous submerged operation.
Network transformers are also employed in buildings, typically in the basement. In such cases, vault - type transformers can be utilized, provided that the room is properly constructed and safeguarded for this purpose.Utilities may also opt for dry - type units and units with less - flammable insulating oils.
Technical Characteristics
A network transformer is equipped with a three - phase primary - side switch, which is capable of opening, closing, or short - circuiting the primary - side connection to ground. Its standard secondary - side voltages are 216Y/125 V and 480Y/277 V. Table 1 below lists the standard specifications.
Transformers with a rated capacity of 1000 kVA or less have an impedance of 5%; for those with a rated capacity exceeding 1000 kVA, the standard impedance is 7%.
The reactance - to - resistance ratio (X/R) generally ranges from 3 to 12. Transformers with lower impedance (such as those with a 4% impedance) exhibit lower voltage drops and higher secondary - side fault currents. (Higher secondary - side fault currents are beneficial for clearing faults in the network.) However, lower impedance comes at a cost – it results in higher circulating currents and poorer load balancing among transformers.
Transformers with a rated capacity of 1000 kVA or less have an impedance of 5%; for those with a rated capacity exceeding 1000 kVA, the standard impedance is 7%.The reactance - to - resistance ratio (X/R) generally ranges from 3 to 12. Transformers with lower impedance (such as those with a 4% impedance) exhibit lower voltage drops and higher secondary - side fault currents. (Higher secondary - side fault currents are beneficial for clearing faults in the network.) However, lower impedance comes at a cost – it results in higher circulating currents and poorer load balancing among transformers.
Grounding connections 
Most network transformers are connected delta – grounded wye.By blocking the zero - sequence current, this connection keeps the grounding current on the primary cables at a low level. Consequently, a highly - sensitive ground - fault relay can be employed on the substation circuit breaker. Blocking the zero - sequence current also reduces the current on the cable neutrals and cable sheaths, including zero - sequence harmonics, predominantly the third harmonic.In the event of a primary line - to - ground fault, the feeder circuit breaker trips, yet the network transformers will continue to backfeed the fault until all network protectors operate (and some may malfunction). At this point, the network transformers backfeed the primary feeder as an ungrounded circuit.
In an ungrounded circuit, a single - phase line - to - ground fault causes a neutral - point shift, which raises the phase - to - neutral voltage of the unfaulted phases to the phase - to - phase voltage level. Non - network loads connected phase - to - neutral will be exposed to this overvoltage.Some networks adopt the grounded wye - grounded wye connection method.
This connection is more suitable for combination feeders. In the event of a primary line - to - ground fault, the feeder circuit breaker trips. For the backfeed current to the primary through the network, the wye - wye connection still provides a grounding reference point, thus reducing the likelihood of overvoltage.The grounded wye - grounded wye connection also decreases the probability of ferroresonance when the transformer undergoes single - pole switching.
Most network transformers are of the core type, with the core structure being either three - legged (three - phase, three - column) or five - legged (three - phase, five - column). The three - legged core, whether it is a stacked core or a wound core, is suitable for a delta - grounded wye connection (but not for a grounded wye - grounded wye connection due to tank heating issues). A five - legged core transformer is suitable for both of the above - mentioned connection types.

 

Give a tip and encourage the author!
Recommended
Why Do Contactors Always Burn Out? Overload and Short-Circuit Protection Must Be Implemented Simultaneously
Contactors are used to close and open loads that require such operations during normal use, particularly for specific activities like medium-voltage public lighting and industrial electric motors.The medium-voltage contactor + fuse combination controller (F-C) can control motors up to 12 kV. However, medium-voltage controllers are also suitable as feeders for other types of loads, especially transformers. For such loads, contactors are usually modified to include mechanical latching, so that the
Echo
09/11/2025
High-Voltage DC Contactor Wiring Essentials: Polarity Requirements and Safety Guidelines
High-Voltage DC Contactors Usually Have Polarity DistinctionsThis is especially true in application scenarios with high current and high voltage.Why Polarity Distinctions ExistArc CharacteristicsDC current has no zero-crossing point, making arc extinction more difficult than that of AC. Polarity (current direction) may affect the stretching and extinguishing effect of the arc.Internal Structural DesignSome contactors optimize arc-extinguishing devices (such as magnetic blowout coils and permanen
Echo
09/09/2025
Working Principle of Low-Voltage Vacuum Contactors and Their Application in DF100A Shortwave Transmitters
In power systems, low-voltage vacuum contactors are used for remotely connecting and disconnecting circuits, as well as frequently starting and controlling AC motors. They can also form electromagnetic starters together with various protection devices.Due to their longer service life, higher reliability, and auxiliary switches compatible with electronic equipment, low-voltage vacuum contactors can fully replace traditional air AC contactors. They are applied in important scenarios across sectors
Echo
09/09/2025
A hybrid DC circuit breaker
Most DC molded-case circuit breakers use natural air arc extinction, and there are typically two arc extinguishing methods: one is conventional opening and closing, where the contacts axially stretch the arc, while the conductive circuit generates a magnetic field that bends and elongates the arc, pulling it lengthwise perpendicular to the arc axis. This not only increases the arc length but also induces lateral motion, enabling air cooling to achieve arc extinction.The other method involves the
Echo
09/02/2025
Related Products
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.