Insulation Dielectric Test of Transformer

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Dielectric Test Definition


The dielectric test of a transformer checks the insulation’s ability to handle voltage without breaking down.


Separate Source Voltage Withstand Test of Transformer


This dielectric test checks the main insulation’s ability to withstand voltage between the winding and the earth.


Procedure


  • All three line terminals of the winding to be tested are connected together.



  • Other winding terminals not under test and the transformer tank should be connected to the earth.



  • Then a single-phase power frequency voltage of shape approximately sinusoidal is applied for 60 seconds to the terminals of the winding under test.



  • The test shall be performed on all the windings one by one.


  • The test is successful if the insulation does not break down during the test.

 

750ffe8af9fa2b8ac85537cdc5a2db18.jpeg

 

In this transformer testing, the peak value of voltage is measured, that is why the capacitor voltage divider with digital peak voltmeter is employed as shown in the diagram above. The peal value multiplied by 0.707 (1/√2) is the test voltage.


The values of test voltage for different fully insulated winding are furnished below in the table.


a3b510e758c200156aaccb1913125fc5.jpeg


Induced Voltage Test of Transformer


19d86833ccd9abc79b3a28c9c1e10767.jpeg

 

The induced voltage test of transformer is intended to check the inter turn and line end insulation as well as main insulation to earth and between windings-

 


  • Keep the primary winding of transformer open circuited.



  • Apply three phase voltage to the secondary winding. The applied voltage should be twice of rated voltage of secondary winding in magnitude and frequency.



  • The test should last for 60 seconds.



  • The test shall start with a voltage lower than 1/3 the full test voltage, and it shall be quickly increased up to desired value.



The test is successful if no break down occurs at full test voltage during test.

Give a tip and encourage the author!
Recommended
SST Technology: Full-Scenario Analysis in Power Generation, Transmission, Distribution, and Consumption
SST Technology: Full-Scenario Analysis in Power Generation, Transmission, Distribution, and Consumption
I. Research BackgroundPower System Transformation NeedsChanges in energy structure are placing higher demands on power systems. Traditional power systems are transitioning toward new-generation power systems, with the core differences between them outlined as follows: Dimension Traditional Power System New-Type Power System Technical Foundation Form Mechanical Electromagnetic System Dominated by Synchronous Machines and Power Electronic Equipment Generation-Side Form M
Echo
10/28/2025
Rectifier vs Power Transformer: Key Differences
Rectifier vs Power Transformer: Key Differences
Differences Between Rectifier Transformers and Power TransformersRectifier transformers and power transformers both belong to the transformer family, but they differ fundamentally in application and functional characteristics. The transformers commonly seen on utility poles are typically power transformers, while those supplying electrolytic cells or electroplating equipment in factories are usually rectifier transformers. Understanding their differences requires examining three aspects: working
Echo
10/27/2025
SST Transformer Core Loss Calculation and Winding Optimization Guide
SST Transformer Core Loss Calculation and Winding Optimization Guide
SST High-Frequency Isolated Transformer Core Design and Calculation Material Characteristics Impact:Core material exhibits varying loss behavior under different temperatures, frequencies, and flux densities. These characteristics form the foundation of overall core loss and require precise understanding of nonlinear properties. Stray Magnetic Field Interference:High-frequency stray magnetic fields around windings can induce additional core losses. If not properly managed, these parasitic losses
Dyson
10/27/2025
Design of a Four-Port Solid-State Transformer: Efficient Integration Solution for Microgrids
Design of a Four-Port Solid-State Transformer: Efficient Integration Solution for Microgrids
The use of power electronics in industry is increasing, ranging from small-scale applications such as chargers for batteries and LED drivers, to large-scale applications like photovoltaic (PV) systems and electric vehicles. Typically, a power system consists of three parts: power plants, transmission systems, and distribution systems. Traditionally, low-frequency transformers are used for two purposes: electrical isolation and voltage matching. However, 50-/60-Hz transformers are bulky and heavy
Dyson
10/27/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.