Weston Type Frequency Meter

Encyclopedia
Field: Encyclopedia
0
China

Weston Frequency Meter Definition


The Weston frequency meter measures frequency by using the deflection of a magnetic needle caused by perpendicular currents in two coils.


Construction


It includes two coils, three inductors, and two resistors arranged in a specific configuration.

 

Circuit Diagram


The diagram shows Coil 1 with a series resistor (R1) and reactance coil (L1), and Coil 2 with a series reactance coil (L2) and parallel resistor (R2).


f61b5b19529ea3da3a85f47797a12a54.jpeg


Working Principle


Axis of both coils are marked as shown. Scale of the meter is calibrated such that at standard frequency the pointer will take position at 45o. Coil 1 contains a series resistor marked R1 and reactance coil marked as L1, while the coil 2 has a series reactance coil marked as L2 and parallel resistor marked as R2. The indcuctor which is marked as L0 is connected in series with the supply voltage in order to reduce the higher harmonic means here this inductor is working as a filter circuit. Let us look at the working of this meter.


When we apply voltage at the standard frequency, the pointer stays at the normal position. If the frequency increases, the pointer moves to the left, indicating a higher frequency. If the frequency decreases, the pointer moves to the right, indicating a lower frequency. If the frequency drops below normal, the pointer crosses the normal position and moves further left.


Let’s examine the internal working of this meter. The voltage drop across an inductor is proportional to the frequency of the source voltage. As the frequency of the applied voltage increases, the voltage drop across inductor L1 increases, which raises the current across Coil 1. This causes the current through Coil 1 to increase and the current through Coil 2 to decrease.


As the current through Coil 1 increases, its magnetic field also increases, causing the magnetic needle to move more to the left, indicating higher frequency. If the frequency decreases, a similar action occurs, but the pointer moves to the right.


Behavior with Frequency Changes


The needle moves left with higher frequencies and right with lower frequencies, reflecting the change in the current through the coils.

 

Give a tip and encourage the author!

Recommended

Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Reclosing Charge Time: Why Does Reclosing Require Charging? What Effects Does Charging Time Have?
1. Function and Significance of Reclosing ChargingReclosing is a protective measure in power systems. After faults such as short circuits or circuit overloads occur, the system isolates the faulty circuit and then restores normal operation through reclosing. The function of reclosing is to ensure continuous operation of the power system, improving its reliability and safety.Before performing reclosing, the circuit breaker must be charged. For high-voltage circuit breakers, the charging time is g