Protection measures of three-phase transformer

Encyclopedia
09/23/2024

Protection measures for use of three-phase transformers


Three-phase transformer may encounter various faults and abnormal working conditions during use, in order to ensure its safe and stable operation, a series of protective measures are usually taken. The following are several common protection measures for three-phase transformers according to the search results:


Gas protection


Gas protection is a protective measure used to reflect the internal failure of the transformer tank and the reduction of the oil level. When the fault in the tank produces slight gas or the oil level drops, the gas protection should be activated at the signal; When a large amount of gas is generated, the circuit breaker on each side of the transformer should be disconnected.


Longitudinal differential protection or current velocity break protection


This protection measure is used to reflect the short-circuit between the transformer winding and the lead line, and the single-phase grounding short-circuit between the neutral point direct grounding system winding and the lead line. It can quickly detect the fault and activate the protection mechanism, cut off the power and avoid the expansion of the fault.


Overcurrent protection


Overcurrent protection is used to reflect the external phase short circuit of the transformer, and as a backup protection for gas protection and differential protection (or current current break protection). This protection can be used as the last line of defense when the gas protection and differential protection fail, cutting off the power supply and protecting the transformer from damage.


Zero sequence current protection


Zero sequence current protection is used to protect the external single-phase grounding short circuit of the system with high grounding current. It detects the presence of zero sequence current and initiates protective action to avoid transformer damage due to ground failure.


Overload protection


Overload protection is used to reflect the symmetric overload of the transformer. This protection only acts on the signal and does not immediately cut off the power supply, but warns the staff that the transformer is overloaded and needs to be adjusted.


Overexcitation protection


Overexcitation protection is used to prevent transformer damage due to overexcitation. When the overexcitation of the transformer exceeds the allowable limit, the overexcitation protection will be activated, sending a signal or acting on the trip, limiting the degree of overexcitation.


Differential protection


Differential protection is an important protection measure, which can reflect the fault of transformer outlet line, bushing and internal short circuit. This kind of protection can be operated instantaneously on each side of the transformer circuit breaker, which is of great significance for the protection of transformer equipment.


Neutral point direct grounding protection


For the transformer directly grounded at the neutral point, when the single phase grounding fault occurs, it will produce a large short circuit current. The ground protection device determines whether the ground fault occurs by detecting the zero sequence current, and acts to remove the fault part in time.


Neutral point is not grounded or protected by arc suppression coil


For the transformer with ungrounded neutral or grounded by arc suppression coil, when the single-phase grounding fault occurs, the grounding current is small, and the zero-sequence voltage protection or insulation monitoring device is usually used to detect the grounding fault.


Temperature protection


The transformer will generate heat during operation, and when the temperature is too high, the insulation performance and service life of the transformer will be affected. The purpose of temperature protection is to monitor the temperature change of the transformer, and when the temperature exceeds the set value, send an alarm signal or act on the trip to prevent the transformer from overheating and damage.


Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
For users, when purchasing a 35kV new energy transformer, choosing between dry-type, mineral oil-filled, or vegetable oil-filled types involves multiple considerations. These include user habits, maintenance-free performance, safety and fire resistance, volume and weight, among others. However, cost differences are undoubtedly one of the most crucial factors.To illustrate the issue intuitively, this paper selects a three-level energy efficiency dual-winding new energy transformer with a rated ca
Ron
07/26/2025
What is the connection group of a transformer?
What is the connection group of a transformer?
Transformer Connection GroupThe connection group of a transformer refers to the phase difference between the primary and secondary voltages or currents. It is determined by the winding directions of the primary and secondary coils, the labeling of their start and end terminals, and the connection mode. Expressed in a clock-like format, there are 12 groups in total, numbered from 0 to 11.The DC method is commonly used to measure the transformer's connection group, mainly to verify whether the con
Vziman
07/26/2025
What is the sequence for powering down the transformer?
What is the sequence for powering down the transformer?
The sequence for shutting down a main transformer is as follows: when de-energizing, the load side should be shut down first, followed by the power supply side. For energizing operations, the reverse order applies: the power supply side is energized first, then the load side. This is because: Energizing from the power supply side to the load side makes it easier to identify the fault range and take prompt judgment and handling measures in case of a fault, preventing the fault from spreading or e
Rockwell
07/26/2025
What are the methods for switching operations of station transformers?
What are the methods for switching operations of station transformers?
Let's take an auxiliary power system with two station transformers as an example. When one station transformer needs to be out of service, there are two operation methods: non-interruptive power supply and instantaneous power interruption. Generally, the method of instantaneous power interruption on the low-voltage side is preferred.The operation method for instantaneous power interruption on the low-voltage side is as follows:Open the 380V power incoming circuit breaker of the corresponding sec
Vziman
07/26/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!