• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What is Circuit Breaker Maintenance?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China


What is Circuit Breaker Maintenance?


Circuit Breaker Maintenance Definition


Circuit breaker maintenance involves switching off, isolating, and regularly checking and servicing the breaker to ensure reliable operation.


13286e5b1757901385d7813530013028.jpeg


Bulk Oil Circuit Breaker


For bulk oil circuit breaker, we should check contact burning. If burning is very light, remove the burn beads and polish the surface. If burning is quite heavy, replace the tips and arcing ring by new set. We should loose and tight the tips few times before final tightening is done.


Additionally, check the extinguishing chamber. Remove it from the breaker unit, wash it with insulating oil, and keep it upside down. Replace any severely burned or damaged parts.


Next, clean and lubricate the circuit breaker mechanism. Remove rust with non-fluffy cotton cloths and lubricate the mechanism, including the gear wheel, with high-grade grease. Remember to lubricate the friction clutch. For minimum oil circuit breaker (MOCB), clean the insulator and remove any carbon deposits with Trichloroethylene or Acetone. Follow the manufacturer’s manual for detailed instructions.


Check the locking pins of the tie rods and all foundation bolts and electrical terminal connections at the circuit breaker power circuit every six months. Tighten them properly after removing any oxide coating.


The proper adjustment of auxiliary switch by ensuring correct NO NC contacts at breaker OFF and ON condition must be checked half yearly and in addition to that the auxiliary switch’s contacts should be cleaned properly with help of hard brushes.


The spring charging motor and mechanism should also be cleaned and associated bearing should also be lubricated half yearly.


Minimum Oil Circuit Breaker (MOCB) Maintenance


In case of MOCB, the breaker should be checked monthly for oil leakage and oil level. If oil leakage is found it must be attended and for low oil level top up oil up to desire level.


Perform a visual inspection of the circuit breaker, its operating mechanism, painting quality, and mechanism kiosk door gasket every quarter. Take proper action if any damage is found.


The oil dash pot in operating mechanism must be checked for oil leakage quarterly if leakage is found, replace the defective and damaged O – rings.It is also highly recommended to ensure the prescribed duty cycle of operation of the breaker including reclosing annually.


Air Blast Circuit Breaker Maintenance


For air blast circuit breaker there are some special cares to be taken in addition to general instruction for maintenance of operating mechanism. Actually for operating mechanisms and for other some features the maintenance processes and schedules are same for all oil circuit breaker, air circuit breaker, SF6 circuit breaker and vacuum circuit breaker.


In air circuit breaker, the air leakage should be checked as and when it is required. If leakage is found, plug the leakage.


The grading capacitors must be checked for oil leakage monthly. If leakage found plug it.Yearly, dew point of the operating air at the outlet of the air dryer should be measured with the help of Dew Point Meter or Hygro Meters.


SF6 and Vacuum Circuit Breaker


As we said earlier for operating mechanisms and for some other features the maintenance processes and schedules are same for all oil circuit breaker, air circuit breaker, SF6 circuit breaker and vacuum circuit breaker.


In addition to that in SF6 CB some extra care to be taken.SF6 circuit breaker must be checked for SF6 gas leakage, if unwanted SF6 low gas pressure alarm comes. This is efficiently done by gas leakage detector.If the circuit breaker is provided with gradient capacitors, these must be checked for oil leakage monthly. If leakage found plug it.Dew point of SF6 should be checked with the help of dew point meter or hygro meters in every 3 to 4 years interval.

  

 


Give a tip and encourage the author!
Recommended
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Expected service life of 30–40 years, front access, compact design equivalent to SF6-GIS, no SF6 gas handling – climate-friendly, 100% dry air insulation. The Nu1 switchgear is metal-enclosed, gas-insulated, featuring a withdrawable circuit breaker design, and has been type-tested according to relevant standards, approved by the internationally recognized STL laboratory.Compliance Standards Switchgear: IEC 62271-1 High-voltage switchgear and controlgear – Part 1: Common specifications for altern
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.