• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What are Faults in Transformer?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China


What are Faults in Transformer?


Definition of Transformer Faults


Faults in transformer refer to issues like insulation breakdowns and core faults that can occur inside or outside the transformer.

 


External Faults in Power Transformer

 


External Short Circuit of Power Transformer


 

Short circuits can happen in two or three phases of the electrical power system. The fault current is usually high, depending on the short-circuited voltage and circuit impedance up to the fault point. This high fault current increases copper loss, causing internal heating in the transformer. It also creates severe mechanical stresses, especially during the first cycle of the fault current.


High Voltage Disturbance in Power Transformer


 

High voltage disturbance in power transformer are of two kinds,



  • Transient Surge Voltage

  • Power Frequency Over Voltage

 


Transient Surge Voltage


High voltage and high frequency surge may arise in the power system due to any of the following causes,

 


  • Arcing ground if neutral point is isolated.

  • Switching operation of different electrical equipment.

  • Atmospheric Lightening Impulse.

 


Whatever may be the causes of surge voltage, it is after all a traveling wave having high and steep wave form and also having high frequency. This wave travels in the electrical power system network, upon reaching in the power transformer, it causes breakdown of the insulation between turns adjacent to line terminal, which may create short circuit between turns.


Power Frequency Over Voltage


There may be always a chance of system over voltage due to sudden disconnection of large load. Although the amplitude of this voltage is higher than its normal level but frequency is same as it was in normal condition. Over voltage in the system causes an increase in stress on the insulation of transformer. As we know that, voltage , increased voltage causes proportionate increase in the working flux.

 

2f0db1edff2b8e96f0313ed94c801420.jpeg

 

This therefore causes, increased in iron loss and proportionately large increase in magnetizing current. The increase flux is diverted from the transformer core to other steel structural parts of the transformer. Core bolts which normally carry little flux, may be subjected to a large component of flux diverted from saturated region of the core alongside. Under such condition, the bolt may be rapidly heated up and destroys their own insulation as well as winding insulation.

 


Under Frequency Effect in Power Transformer


As, voltage as the number of turns in the winding is fixed.From, this equation it is clear that if frequency reduces in a system, the flux in the core increases, the effect are more or less similar to that of the over voltage.

 

c5e82df6f5477f495e2253467fcd55f8.jpeg

 

Internal Faults in Power Transformer


The principle faults which occurs inside a power transformer are categorized as,

 


  • Insulation breakdown between winding and earth

  • Insulation breakdown in between different phases

  • Insulation breakdown in between adjacent turns i.e. inter – turn fault

  • Transformer core fault

 


Internal Earth Faults in Power Transformer


Internal Earth Faults in a Star Connected Winding with Neutral Point Earthed through an Impedance


In a star-connected winding with the neutral point earthed through an impedance, fault current depends on the earthing impedance and the distance from the fault point to the neutral. The voltage at the fault point is higher if it is further from the neutral, leading to higher fault current. Fault current also depends on the leakage reactance of the winding portion across the fault point and neutral, but this is usually low compared to earthing impedance.


Internal Earth Faults in a Star Connected Winding with Neutral Point Solidly Earthed

 


In this case, earthing impedance is ideally zero. The fault current is dependent up on leakage reactance of the portion of winding comes across faulty point and neutral point of transformer. The fault current is also dependent on the distance between neutral point and fault point in the transformer.


As said in previous case the voltage across these two points depends upon the number of winding turn comes across faulty point and neutral point. So in star connected winding with neutral point solidly earthed, the fault current depends upon two main factors, first the leakage reactance of the winding comes across faulty point and neutral point and secondly the distance between faulty point and neutral point. 


But the leakage reactance of the winding varies in complex manner with position of the fault in the winding. It is seen that the reactance decreases very rapidly for fault point approaching the neutral and hence the fault current is highest for the fault near the neutral end. So at this point, the voltage available for fault current is low and at the same time the reactance opposes the fault current is also low, hence the value of fault current is high enough. 


Again at fault point away from the neutral point, the voltage available for fault current is high but at the same time reactance offered by the winding portion between fault point and neutral point is high. It can be noticed that the fault current stays a very high level throughout the winding. In other word, the fault current maintain a very high magnitude irrelevant to the position of the fault on winding.


Internal Phase to Phase Faults in Power Transformer


Phase to phase fault in the transformer are rare. If such a fault does occur, it will give rise to substantial current to operate instantaneous over current relay on the primary side as well as the differential relay.


Inter Turns Fault in Power Transformer


Power transformer connected with electrical extra high voltage transmission system, is very likely to be subjected to high magnitude, steep fronted and high frequency impulse voltage due to lightening surge on the transmission line. The voltage stresses between winding turns become so large, it can not sustain the stress and causing insulation failure between inter – turns in some points. Also LV winding is stressed because of the transferred surge voltage. Very large number of power transformer failure arises from fault between turns. Inter turn fault may also be occurred due to mechanical forces between turns originated by external short circuit.


Core Fault in Power Transformer


If any part of the core lamination is damaged or bridged by a conducting material, it can cause eddy current and local overheating. This can also happen if the insulation of bolts used to tighten the core laminations fails. These faults cause severe local heating but don’t significantly affect the transformer input and output current, making them hard to detect with standard electrical protection schemes. Excessive overheating can break down transformer oil, releasing gases that accumulate in the Buchholz relay and trigger an alarm. 


Give a tip and encourage the author!
Recommended
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
What are the causes of failures in low-voltage switchgear circuit breakers themselves?
Based on years of field statistics on switchgear accidents, combined with analysis focusing on the circuit breaker itself, the main causes have been identified as: failure of operation mechanism; insulation faults; poor breaking and closing performance; and poor conductivity.1.Failure of Operation MechanismFailure of operation mechanism manifests as delayed operation or unintended operation. Since the most basic and important function of a high-voltage circuit breaker is to operate correctly and
Felix Spark
11/04/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Compact Air-Insulated RMUs for Retrofit & New Substations
Compact Air-Insulated RMUs for Retrofit & New Substations
Air-insulated ring main units (RMUs) are defined in contrast to compact gas-insulated RMUs. Early air-insulated RMUs used vacuum or puffer-type load switches from VEI, as well as gas-generating load switches. Later, with the widespread adoption of the SM6 series, it became the mainstream solution for air-insulated RMUs. Similar to other air-insulated RMUs, the key difference lies in replacing the load switch with an SF6-encapsulated type—where the three-position switch for load and grounding is
Echo
11/03/2025
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Climate-Neutral 24kV Switchgear for Sustainable Grids | Nu1
Expected service life of 30–40 years, front access, compact design equivalent to SF6-GIS, no SF6 gas handling – climate-friendly, 100% dry air insulation. The Nu1 switchgear is metal-enclosed, gas-insulated, featuring a withdrawable circuit breaker design, and has been type-tested according to relevant standards, approved by the internationally recognized STL laboratory.Compliance Standards Switchgear: IEC 62271-1 High-voltage switchgear and controlgear – Part 1: Common specifications for altern
Edwiin
11/03/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.