Types of Capacitor Bank

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Types of Capacitor Bank Definition


Capacitor banks are defined as groups of capacitors connected together to improve the power factor in electrical systems.


 

  • Externally fused capacitor bank.

  • Internally fused capacitor bank.

  • Fuse less capacitor bank.


Externally Fused Capacitor Bank


In this type of capacitor bank, each capacitor unit has an external fuse. If a unit develops a fault, its external fuse will blow. This disconnection allows the bank to continue operating without interruption. These capacitor units are connected in parallel.


With several capacitor units connected in parallel per phase, the failure of one unit doesn’t greatly affect the bank’s performance. The phase with the missing unit will have lower capacitance, causing higher voltage in the other two phases. If each unit has a low enough capacity, the voltage imbalance will be minimal. This is why the VAR rating per capacitor unit in a bank is limited to a specified amount.


In the externally fused capacitor bank, the faulty unit can easily be identified by identifying blown out fuse unit through visual inspection.The rating of capacitor unit is typically from 50 KVAR to 40 KVAR.The main drawback of this type of capacitor bank is that, on failure of any fuse unit, there will be unbalance sensed, even all capacitor units of the bank are healthy.


Internally Fused Capacitor Bank


The entire capacitor bank is built as a single arrangement, with multiple capacitor elements connected in parallel and series according to the bank’s rating. Each element is individually protected with a fuse, all housed within the same casing, making it an internally fused capacitor bank. Each element has a very small rating, so if one fails, it doesn’t significantly affect the bank’s performance. These banks can operate satisfactorily even if more than one element is out of service.


The main drawback of this bank is that, on failure of many number of capacitor elements, the entire bank is to be replaced. There is no scope of single unit replacement.The main advantages is that, it is quite easy to install and also easy to maintain.


Fuse-less Capacitor Bank


In this type of capacitor bank, the required number of fuse units is connected in series to form a capacitor string. The necessary number of these strings is then connected in parallel to form a capacitor bank per phase. Three similar per-phase banks are connected in star or delta to create a complete three-phase capacitor bank.


The units in these strings are not protected by any internal or external fuses. If one unit in a string fails due to a short circuit, the current through the string doesn’t change much because many other capacitors are connected in series. The bank can continue running for a long time before the faulty unit needs replacement, which is why fuses aren’t needed to isolate faulty units immediately.


Advantages of Fuse Less Capacitor Bank


The main advantages of fuse less capacitor bank are,


  • They are less expensive then fused capacitor banks.



  • They require less space compared to fused capacitor bank.



  • Less chance of bird fault, snake fault or rat fault as the inter connecting wire can be insulated properly in fuse less capacitor bank.

 


Disadvantages of Fuse Less Capacitor Bank


  • There are also some disadvantages of fuse less capacitor bank.



  • Any earth fault in the bank, unit, such as bushing fault, insulation failure between tank and live part of the capacitor, should be cleared immediately by tripping of circuit brake associated with this bank as there is no provision of any fuse.



  • For replacement of any capacitor unit, only identical spare is required. It cannot be managed by available standard capacitor unit. So, there must be sufficient stock of identical capacitor units available at site which is an extra investment.



  • Some time it becomes difficult to locate actual faulty unit of the bank only by visual inspections. Then the time required to replace actual faulty unit will be higher.



  • Sophisticated relay and control system are essential for fuse less capacitor bank. The relay system of the bank should also be capable of tripping the circuit breaks associated with it in the event of input power failure to the relay.



  • External reactor is required to limit transient current in the capacitor.

 

Give a tip and encourage the author!
Recommended
 Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes of Fire and Explosion in Oil Circuit Breakers When the oil level in an oil circuit breaker is too low, the oil layer covering the contacts becomes too thin. Under the effect of the electric arc, the oil decomposes and releases flammable gases. These gases accumulate in the space beneath the top cover, mixing with air to form an explosive mixture, which can ignite or explode under high temperature. If the oil level inside the tank is too high, the released gases have limited space to expan
Felix Spark
11/06/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
Why Monitoring Accuracy Matters in Power Quality Systems
Why Monitoring Accuracy Matters in Power Quality Systems
The Critical Role of Monitoring Accuracy in Power Quality Online DevicesThe measurement accuracy of online power quality monitoring devices is the core of the power system’s “perception capability,” directly determining the safety, economy, stability, and reliability of power supply to users. Inadequate accuracy leads to misjudgment, incorrect control, and flawed decision-making—potentially causing equipment damage, economic losses, or even grid failures. Conversely, high accuracy enables precis
Oliver Watts
10/30/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.