Construction of a Shunt Reactor

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Shunt Reactor Definition


A shunt reactor is used to neutralize excess capacitive reactive power on long electrical transmission lines.


Core of Shunt Reactor


Shunt reactors typically use a gapped core, built from Cold Rolled Grain Oriented Silicon Steel to cut down on hysteresis losses. The steel sheets are laminated to lessen eddy current losses. Radial gaps, placed by high electrical modulus spacers between lamination packets, enhance efficiency. Typically, a 5-limb, 3-phase core structure in a shell form is employed, where only the three inner limbs are gapped.


Winding of Shunt Reactor


There is nothing special about winding of a reactor. This is mainly made of copper conductors. The conductors are paper insulated. Insulated spacers are provided between turns to maintain the path for oil circulation. This arrangement helps for efficient cooling of the winding.


Cooling System of Reactor


The ONAN (Oil Natural Air Natural) cooling system, sufficient for even high-voltage shunt reactors due to their low current operation, employs a radiator bank linked to the main tank for enhanced cooling.


Tank of Reactor


For UHV and EHV systems, the main tank, often a bell tank type, is crafted from thick steel sheets welded together to endure both full vacuum and atmospheric pressure. These tanks are also designed for easy transport by road and rail.


Conservator of Reactor


Conservator is provided at the top of the tank with main tank to conservator connecting pipe line of suitable diameter. The conservator is generally horizontally aligned cylindrical tank, to provide adequate space to the oil for expansion due to temperature rise.


 Flexible separator between air and oil or air cell is provided in the conservator for the said purpose. The conservator tank is also equipped with a magnetic oil gauge to monitor the oil level in the reactor. The magnetic oil gauge also gives an alarm through a normally open (NO) DC contact, attached to it when oil level falls below a preset level due to oil leakage or any other reason.


0a9031d8637ed5dc37eda4c6660d7486.jpeg


Pressure Relief Device


Due to huge fault inside the reactor there may be sudden and excessive expansion of oil inside the tank. This huge oil pressure generated in the reactor should be released immediately along with separation of the reactor from the live power system. 


Pressure Relief Device does the job. This is a spring loaded mechanical device. This is fitted on the roof of the main tank. At the event of actuation, the upward pressure of the oil in tank becomes greater than the downward spring pressure, as a result there will be an opening in the valve disc of the device through which the expanded oil comes out to relief the pressure formed inside the tank.


 There is a mechanical lever attached to the device which is normally in horizontal position. When the device is actuated, this lever becomes vertical. By observing the alignment of the lever even from ground level one can predict whether the Pressure Relief Device (PRD) has been operated or not. The PRD is accompanied with a trip contact to trip the shunt reactor at the event of actuation of the device.


N B: – PRD or such type of device cannot be reset from remote once it actuated. It can only be reset manually by moving the lever to its original horizontal position.


Buchholz Relay


One Buchholz relay is fitted across the pipe connecting the conservator tank and main tank. This device collects gases generated in the oil and actuates the alarm contact attached to it. It has also a trip contact which is actuated at the event of sudden accumulation of gas in the device or rapid flow of oil (oil surge) through the device.


Silica Gel Breather


When oil becomes hot, it is expanded thus air from conservator or air shell (where air shell is used) comes out. But during contraction oil, air from the atmosphere enters into conservator or air shell (where air shell is used). This process is called breathing of the oil immersed equipment (like transformer or reactor). 


During breathing, obviously moisture can enter into the equipment if it is not taken care of. An pipe from conservator tank or air shell is fitted with a container filled with silica gel crystal. When air is passed through it, the moisture is absorbed by the silica gel.


Winding Temperature Indicator


Winding temperature indicator is a kind of indicating meter associated with a relay. This consists of a sensor bulb placed in an oil filled pocket on the roof of reactor tank. There are two capillary tubes between sensor bulb and the instrument housing. 


One capillary tube is connected to the measuring bellow of the instrument. Other capillary tube connected to the compensating bellow fitted in the instrument. The measuring system, i.e. sensor bulb, both capillary tubes and both bellows are filled with a liquid which changes its volume when temperature changes. 


The pocket in which the sensor bulb is immersed, is surrounded by a heating coil which is fed by a current proportional to the current flowing through the winding of reactor. Gravity operated NO contacts are attached to the pointer system of the instrument to provider high temperature alarm and trip respectively.


Oil Temperature Indicator


The oil temperature indicator, featuring a sensor bulb in an oil-filled pocket at the reactor tank’s hottest point, uses two capillary tubes to link the sensor with the instrument’s measuring and compensating bellows. These components are filled with a liquid that expands or contracts with temperature changes, providing accurate temperature readings.


Bushing


The winding terminals of each phase comes out from the reactor boy through an insulated bushing arrangement. In high voltage shunt reactor, the bushings are oil filled. The oil is sealed inside the bushing that means there is no link between the oil inside the bushing and oil inside the main tank. Oil level gauge is provided on the expansion chamber of the condenser bushings.

 

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
Why Monitoring Accuracy Matters in Power Quality Systems
Why Monitoring Accuracy Matters in Power Quality Systems
The Critical Role of Monitoring Accuracy in Power Quality Online DevicesThe measurement accuracy of online power quality monitoring devices is the core of the power system’s “perception capability,” directly determining the safety, economy, stability, and reliability of power supply to users. Inadequate accuracy leads to misjudgment, incorrect control, and flawed decision-making—potentially causing equipment damage, economic losses, or even grid failures. Conversely, high accuracy enables precis
Oliver Watts
10/30/2025
How Does Power Dispatching Ensure Grid Stability and Efficiency?
How Does Power Dispatching Ensure Grid Stability and Efficiency?
Electric Power Dispatching in Modern Power SystemsThe power system is a critical infrastructure of modern society, providing essential electrical energy for industrial, commercial, and residential use. As the core of power system operation and management, electric power dispatching aims to meet electricity demand while ensuring grid stability and economic efficiency.1. Basic Principles of Electric Power DispatchingThe fundamental principle of power dispatching is to balance supply and demand by
Echo
10/30/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.