What is a Phase Synchronizing Device?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China


What is a Phase Synchronizing Device?


Phase Synchronizing Device Definition


A Phase Synchronizing Device (PSD) is defined as a device that synchronizes the switching of circuit breaker poles to the zero crossing of the phase voltage or current waveform.


Controlled Switching Device


Also known as a Controlled Switching Device (CSD), it ensures accurate timing during circuit breaker operations.


Voltage and Current Synchronization


The PSD uses voltage and current waveforms to identify zero crossings and synchronize breaker operations accordingly.


When switching off a circuit breaker to cut an inductive load, it’s best to interrupt the current at the zero crossing of the current waveform. However, this is difficult to achieve exactly. In normal circuit breakers, current interruption occurs near, but not exactly at, the zero crossing point. Because the load is inductive, this sudden interruption causes a high rate of current change (di/dt), resulting in high transient voltage in the system.


c9c04418569008f87aa07c25b8fbd190.jpeg


In low or medium voltage power systems, transient voltage during circuit breaker operation may not significantly affect performance. However, in extra and ultra-high voltage systems, it is more impactful. If the circuit breaker contacts are not sufficiently separated at the moment of interruption, re-ionization can occur due to transient overvoltage, leading to re-established arcing.


When we switch on an inductive load like transformer or reactor, and if the circuit breaker closes the circuit near to the voltage zero crossing, there will be high DC component of current. This may saturate the core of transformer or reactor. This leads to a high inrush current in the transformer or reactor.


When connecting a capacitive load, like a capacitor bank, it’s best to switch on the circuit breaker at the zero crossing of the system voltage waveform.

 

c2926e255baf7fcd90674da29785a8fa.jpeg

 

e866b0ce6ab0f753063478d3f7592b4e.jpeg

 

Otherwise due to sudden change in voltage during switching, high inrush current is created in the system. This may be followed by over voltage in the system too.


The inrush current along with over voltage stress mechanically and electrically, the capacitor bank and other equipment in line.


In circuit breaker, all three phases usually open or close almost simultaneously. However, there is a 6.6 ms time gap between the zero crossings of adjacent phases in a three-phase system.


This device takes voltage waveform from potential transformer of bus or load, current waveform from current transformers of the load, auxiliary contact signal and reference contact signal from circuit breaker, closing and opening command from control switch of the circuit breaker installed in control panel.


Voltage and current signal from each phase are required to identify exact instant of zero crossing of the waveform of individual phase. Breaker contact signals are required to calculate the operational delay of the circuit breaker, so that the opening or closing pulse to the breaker can be send accordingly, to match the interruption and zero crossing of either current or voltage wave, as per requirement.


9094d53b3b2a66d5c5cb29fc685f977f.jpeg


This device is dedicated for manual operation of the circuit breaker. During faulty tripping, the trip signal to the circuit breaker is directly sent from the protection relay assembly, bypassing the device. The Phase Synchronizing Device or PSD may also be associated with a bypass switch which can bypass the device from the system if required in any situation.


Inductive Load Management


Switching on inductive loads at the right moment prevents high inrush currents that can damage equipment.


Capacitive Load Switching


Proper timing when switching capacitive loads reduces the risk of high inrush currents and overvoltage.



Give a tip and encourage the author!
Recommended
What are the safety precautions and guidelines for using AC load banks?
What are the safety precautions and guidelines for using AC load banks?
AC load banks are electrical devices used to simulate real-world loads and are widely applied in power systems, communication systems, automation control systems, and other fields. To ensure personal and equipment safety during use, the following safety precautions and guidelines must be observed:Select an appropriate AC load bank: Choose an AC load bank that meets actual requirements, ensuring its capacity, voltage rating, and other parameters satisfy the intended application. Additionally, sel
Echo
11/06/2025
What should be noted when installing a Type K thermocouple?
What should be noted when installing a Type K thermocouple?
Installation precautions for Type K thermocouples are critical to ensuring measurement accuracy and extending service life. Below is an introduction to the installation guidelines for Type K thermocouples, compiled from highly authoritative sources:1.Selection and Inspection Select the appropriate thermocouple type: Choose the right thermocouple based on the temperature range, medium properties, and required accuracy of the measurement environment. Type K thermocouples are suitable for temperatu
James
11/06/2025
 Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes of Fire and Explosion in Oil Circuit Breakers When the oil level in an oil circuit breaker is too low, the oil layer covering the contacts becomes too thin. Under the effect of the electric arc, the oil decomposes and releases flammable gases. These gases accumulate in the space beneath the top cover, mixing with air to form an explosive mixture, which can ignite or explode under high temperature. If the oil level inside the tank is too high, the released gases have limited space to expan
Felix Spark
11/06/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.