When two parts of an electrical network with the same operating voltage are coupled, a phase displacement switching phenomenon occurs if their equivalent sources have different phase angles, with some or all phases being 180° out of phase. During the switching operation, the circuit breaker encounters source voltages with differing phase angles, leading to the presence of phase-displaced currents in the connection. These currents must be reliably interrupted by the circuit breakers on both sides of the connection.
Specifically, the phase angle difference between the rotating vectors representing the source voltages results in out-of-sync instantaneous voltage waveforms, causing significant transient currents and voltage stresses at the moment of switching. For transient recovery voltage (TRV), this switching task is characterized by active power sources on both sides of the circuit breaker, increasing the complexity and challenges of the switching operation.
As shown in Figure 1, assume that power sources S1 and S2 represent two sources with different phase angles. When the circuit breaker switches between these two sources, the phase angle difference can lead to a substantial increase in transient current, imposing greater breaking demands on the circuit breaker. Therefore, the circuit breaker must have sufficient capability to handle these high-stress conditions, ensuring safe and reliable switching operations.
Key Points Summary
In the previously discussed fault switching tasks, the Transient Recovery Voltage (TRV) component on the load side ultimately decays to zero. However, in phase displacement switching, the TRV component on the S2 side gradually decays to the power frequency recovery voltage (RV) of the S2 source. As shown in Figure 2, it is assumed that the voltage phase difference between the two sources is 90°, and the short-circuit reactors have equal impedance.
Therefore, the primary feature of phase displacement switching operation is exceptionally high TRV peaks, while the Rate of Rise of Restriking Voltage (RRRV) and current remain relatively moderate. Given that the TRV peak under phase displacement conditions is the highest among all switching operations, it is typically used as a benchmark for evaluating other complex switching conditions, such as clearing faults on long-distance transmission lines or handling faults on series-compensated lines.
Key Points Summary:
In the previously discussed fault switching scenarios, the Transient Recovery Voltage (TRV) component on the load side decays to zero in all cases. However, in phase displacement switching, the TRV component on the side decays to the power frequency recovery voltage (RV) of the source. This behavior is illustrated in Figure 2, where it is assumed that the voltage phase difference between the two sources is 90°, and the short-circuit reactors are considered equal.
In the previously discussed fault switching scenarios, the Transient Recovery Voltage (TRV) component on the load side always decays to zero. However, in phase displacement switching, the TRV component on the side decays to the power frequency recovery voltage (RV) of the source. As shown in Figure 2, this assumes a 90° phase difference between the two power sources and equal short-circuit reactors.
Therefore, the key characteristics of phase displacement switching operation are:
Given that the TRV peak under phase displacement conditions is the highest among all switching modes, this scenario is often used as a reference for evaluating other special switching conditions, such as:
Figure 3 illustrates two scenarios that can lead to phase displacement conditions. In the first scenario (left image), a generator is inadvertently connected to the grid by a circuit breaker at an incorrect phase angle. In the second scenario (right image), different parts of the transmission network lose synchronization, often due to a short circuit occurring somewhere in the network.
In both cases, phase-displaced currents flow through the network, which must be reliably interrupted by the circuit breakers. These situations pose significant challenges to the power system, as the phase displacement can result in high transient currents and voltages, requiring the circuit breakers to handle these extreme conditions effectively.
When using a step-up transformer, the switching between the generator and the power system can occur on either the high-voltage (HV) side or the medium-voltage (MV) side of the transformer. This switching can happen not only during system faults or power plant trips but also during synchronization and desynchronization events.
The severity of out-of-phase conditions depends on:
To address these challenges, power plants are equipped with various protective and control devices:
Figure 4 illustrates this typical layout, showing the connection between the step-up transformer, the generator, and the power system, as well as the configuration of the associated protective and control devices.
Switching between two power systems typically occurs in situations with power unbalance and system instability. Examples refer to large system disturbances, situations during system restoration, and due to the mis-operation of protection systems.
The more important transmission lines may be equipped with an out-of-phase blocking in their protection system and/or a special system-wide protection may be applied to prevent separation of the systems under severe out-of-phase conditions.
Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!