Pneumatic operating mechanism in switchgears

Edwiin
01/09/2025

Pneumatic Mechanisms in High-Voltage Air Blast Circuit Breakers
Pneumatic mechanisms are commonly used with air blast circuit breakers to facilitate the opening and closing operations. In some designs, these mechanisms are entirely pneumatic, eliminating the need for solid mechanical links between the operating mechanism and the contacts. Other designs use an air piston to drive the closing linkage and charge the opening springs.

Typical Pneumatic Mechanism in HV Air Blast Circuit Breakers
Closing Sequence:

Air Supply:

  • Air is supplied through a filter in the air-inlet block (1) to the inlet manifold and main valve block (2). From there, it travels through a connecting pipe to the pilot valve block (4).
  • Under normal conditions, all valves are closed, and there is no pressure within the main body of the unit.

Initiating the Closing Operation:

  • During the closing operation, the solenoid (5) is energized, which opens the pilot valve.
  • Pressurized air then enters the body (3), forcing down a servo-piston onto a bell crank. This action, transmitted through a toggle mechanism (7), raises the main valve stem (6), thereby opening the main valve.

Completion of the Closing Operation:

  • Once initiated, the closing movement must be completed. A one-way ball valve ensures that the main valve remains open until the circuit breaker mechanism stroke is fully executed, independent of the electrical control system.
  • The pressurized air passes through the now-open main valve to the circuit breaker's closing cylinder, completing the closing sequence.

Key Components and Their Functions:

  • Air-Inlet Block (1): Filters and supplies air to the system.
  • Main Valve Block (2): Controls the flow of pressurized air to the closing cylinder.
  • Pilot Valve Block (4): Regulates the initial flow of air to activate the main valve.
  • Solenoid (5): Energizes to open the pilot valve.
  • Servo-Piston: Converts pneumatic force into mechanical motion.
  • Bell Crank and Toggle Mechanism (7): Transmits the force from the servo-piston to raise the main valve stem.
  • Main Valve Stem (6): Opens the main valve to allow air flow to the closing cylinder.
  • One-Way Ball Valve: Ensures the main valve stays open until the closing operation is complete.

This mechanism ensures reliable and controlled operation of high-voltage air blast circuit breakers, maintaining safety and performance standards in critical applications.

Edwiin

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

Online condition monitoring device (OLM2) on high voltage Circuit Breakers
Online condition monitoring device (OLM2) on high voltage Circuit Breakers
This device is capable of monitoring and detecting various parameters according to the specifications outlined:SF6 Gas Monitoring:Utilizes a specialized sensor for measuring SF6 gas density.Capabilities include measuring gas temperature, monitoring SF6 leak rates, and calculating the optimal date for refilling.Mechanical Operation Analysis:Measures operational times for closing and opening cycles.Evaluates primary contacts separation speed, damping, and contact overtravel.Identifies signs of mec
Edwiin
02/13/2025
Anti pumping function in circuit breakers operating mechanism
Anti pumping function in circuit breakers operating mechanism
The anti - pumping function stands as a crucial characteristic of control circuits. In the absence of this anti - pumping function, assume that a user connects a maintained contact within the closing circuit. When the circuit breaker is closed onto a fault current, the protective relays will promptly trigger a tripping action. However, the maintained contact in the closing circuit will attempt to close the breaker (once again) onto the fault. This repetitive and dangerous process is referred to
Edwiin
02/12/2025
Ageing phenomena of current pass blades in high voltage disconnector switch
Ageing phenomena of current pass blades in high voltage disconnector switch
This failure mode has three primary origins:Electrical Causes: The switching of currents, such as loop currents, can lead to localized wear. At higher currents, an electric arc may burn at a specific spot, increasing the local resistance. As more switching operations occur, the contact surface wears down further, causing an increase in resistance.Mechanical Causes: Vibrations, often due to wind, are the main contributors to mechanical aging. These vibrations cause abrasion over time, leading to
Edwiin
02/11/2025
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Transient Recovery Voltage (TRV) stress similar to that encountered during a short-line fault can also occur due to the busbar connections on the supply side of a circuit breaker. This specific TRV stress is known as Initial Transient Recovery Voltage (ITRV). Given the relatively short distances involved, the time to reach the first peak of ITRV is typically less than 1 microsecond. The surge impedance of the busbars within a substation is generally lower compared to that of overhead lines.The f