How can we reduce the starting torque of an induction motor?

Encyclopedia
11/08/2024

(1) Stator winding series resistance or reactance start

Principle: By connecting a resistor or reactor in series with the stator winding of the motor, the voltage drop across the resistor or reactor reduces the voltage applied to the motor winding below the source voltage, thereby reducing the starting torque. After starting, the resistor or reactor is short-circuited to allow the motor to operate at rated voltage. This method is suitable for cage-type induction motors with moderate capacity requiring smooth starting. However, the starting resistor consumes a certain amount of power and should not be started frequently. Additionally, the starting torque decreases due to the reduced starting current.

(II) Using the Reduced Voltage Starting Method

1. Autotransformer Voltage Reduction Starting

Principle: When starting the electric motor, connect the three-phase AC power supply to the electric motor through an autotransformer. The autotransformer can be selected with different transformer voltage taps according to the allowed starting current and the required starting torque, reducing the voltage applied to the electric motor and thus reducing the starting torque. After the start-up is complete, the autotransformer is disconnected, allowing the electric motor to be directly connected to the three-phase power supply for normal operation. It is suitable for larger capacity motors and has the advantages of compact line structure and no restrictions on the wiring mode of the motor windings.

2. Y-Δ Starting (for three-phase induction motors)

Principle: For three-phase induction motors that are normally connected in a delta configuration during operation, the starting process begins with a Y-shaped connection. At this point, the voltage applied to each phase winding is One third of the square root times the normal operating voltage, resulting in a lower voltage and, consequently, a reduction in starting current and torque. After the start is complete, the motor is switched back to the delta configuration for normal operation. This method is simple and economical, but it significantly reduces the starting torque, making it suitable for light load or no-load starting scenarios.

(3) Adjust the load characteristics of the motor

Principle: If the inertia of the load driven by the motor is large or the torque characteristic of the load can be adjusted during startup, increasing the resistance torque of the load appropriately (e.g., using a braking device for certain mechanical loads to apply resistance at the moment of startup) can relatively reduce the effective torque output of the motor during startup, thus achieving the effect of reducing the starting torque. However, this method requires careful operation based on the specific load conditions to avoid any adverse effects on the motor and load equipment.

Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
For users, when purchasing a 35kV new energy transformer, choosing between dry-type, mineral oil-filled, or vegetable oil-filled types involves multiple considerations. These include user habits, maintenance-free performance, safety and fire resistance, volume and weight, among others. However, cost differences are undoubtedly one of the most crucial factors.To illustrate the issue intuitively, this paper selects a three-level energy efficiency dual-winding new energy transformer with a rated ca
Ron
07/26/2025
What is the connection group of a transformer?
What is the connection group of a transformer?
Transformer Connection GroupThe connection group of a transformer refers to the phase difference between the primary and secondary voltages or currents. It is determined by the winding directions of the primary and secondary coils, the labeling of their start and end terminals, and the connection mode. Expressed in a clock-like format, there are 12 groups in total, numbered from 0 to 11.The DC method is commonly used to measure the transformer's connection group, mainly to verify whether the con
Vziman
07/26/2025
What is the sequence for powering down the transformer?
What is the sequence for powering down the transformer?
The sequence for shutting down a main transformer is as follows: when de-energizing, the load side should be shut down first, followed by the power supply side. For energizing operations, the reverse order applies: the power supply side is energized first, then the load side. This is because: Energizing from the power supply side to the load side makes it easier to identify the fault range and take prompt judgment and handling measures in case of a fault, preventing the fault from spreading or e
Rockwell
07/26/2025
What are the methods for switching operations of station transformers?
What are the methods for switching operations of station transformers?
Let's take an auxiliary power system with two station transformers as an example. When one station transformer needs to be out of service, there are two operation methods: non-interruptive power supply and instantaneous power interruption. Generally, the method of instantaneous power interruption on the low-voltage side is preferred.The operation method for instantaneous power interruption on the low-voltage side is as follows:Open the 380V power incoming circuit breaker of the corresponding sec
Vziman
07/26/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!