Why does an induction motor draw more current at starting than at running?

Encyclopedia
11/09/2024

An induction motor (Induction Motor) draws more current during start-up than during operation due to the electromagnetic characteristics inside the motor at the start-up stage. Here is a detailed explanation:

1. High Current Demand During Start-Up

1.1 Initial Flux Establishment

No Initial Rotor Field: At start-up, the rotor is stationary and has no initial rotating magnetic field. The rotating magnetic field produced by the stator needs to establish a magnetic flux in the rotor.

High Induced Current: To establish this initial flux, the stator must generate a strong magnetic field, which causes a large current to flow through the stator windings.

1.2 Low Power Factor

Lagging Current: At start-up, since the rotor is not yet rotating, there is a large phase difference between the rotor current and the stator current, resulting in a very low power factor.

Reactive Power Demand: A low power factor means that most of the current is reactive current, used to establish the magnetic field rather than doing useful work.

2. Lower Current Demand During Operation

2.1 Approaching Synchronous Speed

Rotor Field Establishment: As the motor begins to rotate and gradually approaches synchronous speed, the magnetic flux in the rotor is also established.

Reduced Slip: Slip is the difference between the rotor speed and the synchronous speed. As slip decreases, the rotor current also decreases.

2.2 Higher Power Factor

Reduced Phase Difference: As the motor speed increases, the phase difference between the rotor current and the stator current decreases, improving the power factor.

Increased Active Power: A higher power factor means that more of the current is used for doing useful work, reducing the demand for reactive current.

3. Comparison of Start-Up Current and Operating Current

Start-Up Current: Typically, the start-up current of an induction motor can be 6 to 8 times the rated operating current, or even higher.

Operating Current: During normal operation, the motor's current stabilizes near the rated value, significantly lower than the start-up current.

4. Start-Up Strategies

To reduce the high current draw during start-up and minimize the impact on the power grid and the motor itself, several start-up strategies are commonly used:

Direct-On-Line Starting (DOL):

Directly connecting the motor to the power supply, suitable for small motors.

Star-Delta Starting:

Connecting the motor in a star configuration during start-up to reduce the start-up current, then switching to a delta configuration once a certain speed is reached for normal operation.

Soft Starter:

Using silicon-controlled rectifiers (SCRs) or other electronic devices to gradually increase the motor voltage, providing a smooth start-up process and reducing the start-up current.

Variable Frequency Drive (VFD):

Adjusting the frequency and voltage of the motor to achieve smooth start-up and speed control.

Summary

An induction motor draws more current during start-up because it needs to establish an initial magnetic flux in the rotor, and the power factor is very low at this stage. As the motor speed increases, the rotor magnetic field is established, slip decreases, and the power factor improves, causing the current to decrease to normal operating levels. By using appropriate start-up strategies, the high start-up current can be effectively reduced, minimizing the impact on the power grid and the motor.

Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
For users, when purchasing a 35kV new energy transformer, choosing between dry-type, mineral oil-filled, or vegetable oil-filled types involves multiple considerations. These include user habits, maintenance-free performance, safety and fire resistance, volume and weight, among others. However, cost differences are undoubtedly one of the most crucial factors.To illustrate the issue intuitively, this paper selects a three-level energy efficiency dual-winding new energy transformer with a rated ca
Ron
07/26/2025
What is the connection group of a transformer?
What is the connection group of a transformer?
Transformer Connection GroupThe connection group of a transformer refers to the phase difference between the primary and secondary voltages or currents. It is determined by the winding directions of the primary and secondary coils, the labeling of their start and end terminals, and the connection mode. Expressed in a clock-like format, there are 12 groups in total, numbered from 0 to 11.The DC method is commonly used to measure the transformer's connection group, mainly to verify whether the con
Vziman
07/26/2025
What is the sequence for powering down the transformer?
What is the sequence for powering down the transformer?
The sequence for shutting down a main transformer is as follows: when de-energizing, the load side should be shut down first, followed by the power supply side. For energizing operations, the reverse order applies: the power supply side is energized first, then the load side. This is because: Energizing from the power supply side to the load side makes it easier to identify the fault range and take prompt judgment and handling measures in case of a fault, preventing the fault from spreading or e
Rockwell
07/26/2025
What are the methods for switching operations of station transformers?
What are the methods for switching operations of station transformers?
Let's take an auxiliary power system with two station transformers as an example. When one station transformer needs to be out of service, there are two operation methods: non-interruptive power supply and instantaneous power interruption. Generally, the method of instantaneous power interruption on the low-voltage side is preferred.The operation method for instantaneous power interruption on the low-voltage side is as follows:Open the 380V power incoming circuit breaker of the corresponding sec
Vziman
07/26/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!