Isolated Induction Generator

Edwiin
05/23/2025

An isolated induction generator refers to an induction machine that is capable of operating as a generator independently, without relying on an external power supply system. As depicted in the following figure, a three - phase delta - connected capacitor bank is connected across the terminals of the machine. This capacitor bank serves to provide the essential excitation for the machine.

The residual flux within the machine serves as the initial excitation source. In cases where residual flux is absent, the machine can be briefly operated as an induction motor to generate the necessary residual flux. A prime mover drives the motor to run slightly above the synchronous speed under no - load conditions. Consequently, a small electromotive force (EMF) is induced in the stator, with its frequency being proportional to the rotor speed.
The voltage across the three - phase capacitor bank induces a leading current in the capacitor bank. This current is nearly equivalent to the lagging current fed back to the generator.
The magnetic flux generated by this current reinforces the initial residual flux, leading to an increase in the total magnetic flux. As a result, the voltage across the machine increases. This rise in voltage prompts an increase in the exciting current, which in turn further elevates the terminal voltage.

At this juncture, the reactive volt - amperes demanded by the generator are equivalent to those supplied by the three - phase delta - connected capacitor bank. The operating frequency hinges on the rotor speed, and any variation in the load has an impact on the rotor's rotational speed. The voltage is predominantly regulated by the capacitive reactance at the operating frequency.
A significant drawback of an isolated induction generator is that when faced with a load having a lagging power factor, the voltage drops precipitously.
This voltage increase persists until the magnetization characteristic curve of the machine intersects with the voltage - current characteristic curve of the capacitor bank. The following graph illustrates the magnetization curve and the V - IC (Voltage - Capacitor Current) characteristic.
Edwiin

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
For users, when purchasing a 35kV new energy transformer, choosing between dry-type, mineral oil-filled, or vegetable oil-filled types involves multiple considerations. These include user habits, maintenance-free performance, safety and fire resistance, volume and weight, among others. However, cost differences are undoubtedly one of the most crucial factors.To illustrate the issue intuitively, this paper selects a three-level energy efficiency dual-winding new energy transformer with a rated ca
Ron
07/26/2025
What is the connection group of a transformer?
What is the connection group of a transformer?
Transformer Connection GroupThe connection group of a transformer refers to the phase difference between the primary and secondary voltages or currents. It is determined by the winding directions of the primary and secondary coils, the labeling of their start and end terminals, and the connection mode. Expressed in a clock-like format, there are 12 groups in total, numbered from 0 to 11.The DC method is commonly used to measure the transformer's connection group, mainly to verify whether the con
Vziman
07/26/2025
What is the sequence for powering down the transformer?
What is the sequence for powering down the transformer?
The sequence for shutting down a main transformer is as follows: when de-energizing, the load side should be shut down first, followed by the power supply side. For energizing operations, the reverse order applies: the power supply side is energized first, then the load side. This is because: Energizing from the power supply side to the load side makes it easier to identify the fault range and take prompt judgment and handling measures in case of a fault, preventing the fault from spreading or e
Rockwell
07/26/2025
What are the methods for switching operations of station transformers?
What are the methods for switching operations of station transformers?
Let's take an auxiliary power system with two station transformers as an example. When one station transformer needs to be out of service, there are two operation methods: non-interruptive power supply and instantaneous power interruption. Generally, the method of instantaneous power interruption on the low-voltage side is preferred.The operation method for instantaneous power interruption on the low-voltage side is as follows:Open the 380V power incoming circuit breaker of the corresponding sec