Blocked Rotor Test of an Induction Motor

Edwiin
05/24/2025

The blocked - rotor test of an induction motor is analogous to the short - circuit test of a transformer. In this test, the motor's shaft is immobilized to prevent any rotation, and the rotor winding is short - circuited. For a slip - ring motor, the rotor winding is short - circuited via the slip rings. In the case of cage motors, the rotor bars are inherently short - circuited. This test is also referred to as the Locked Rotor Test. The circuit diagram for the blocked - rotor test is presented below:

A reduced voltage at a reduced frequency is supplied to the stator via a three - phase autotransformer, ensuring that the full - load rated current circulates in the stator. The blocked - rotor test yields the following three measurements:
  • Total power input during short - circuit Psc: This is the algebraic sum of the readings from the two wattmeters. The power input during the blocked - rotor test is equivalent to the combined copper losses of the stator and rotor for all three phases. Since a reduced voltage is applied to the stator, thereby preventing rotor rotation, core and mechanical losses can be disregarded.
  • Ammeter reading

  • Reading of the voltmeter

where cosϕ represents the power factor of the short - circuit. The equivalent resistance of the motor, referred to the stator side, is expressed by the following equation:

The equivalent impedance of the motor referred to the stator side is given by the equation shown below:

The equivalent reactance of the motor referred to the stator side is given by the equation shown below.

The blocked - rotor test is carried out under normal operating conditions, with the rotor current and frequency being in their typical states. Generally, for an induction motor, the slip typically ranges from 2% to 4%. When the stator frequency is 50 hertz under normal conditions, the resulting rotor frequency falls within the range of 1 to 2 hertz.
This test should be executed at a reduced frequency. To achieve accurate results, the blocked - rotor test is performed at a frequency that is 25% or less of the rated frequency. The leakage reactances at the rated frequency are derived based on the principle that reactance is proportional to frequency.
Nevertheless, for motors with a rating of less than 20 kilowatts, the influence of frequency is negligible, and the blocked - rotor test can be directly conducted at the rated frequency.
Edwiin

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
For users, when purchasing a 35kV new energy transformer, choosing between dry-type, mineral oil-filled, or vegetable oil-filled types involves multiple considerations. These include user habits, maintenance-free performance, safety and fire resistance, volume and weight, among others. However, cost differences are undoubtedly one of the most crucial factors.To illustrate the issue intuitively, this paper selects a three-level energy efficiency dual-winding new energy transformer with a rated ca
Ron
07/26/2025
What is the connection group of a transformer?
What is the connection group of a transformer?
Transformer Connection GroupThe connection group of a transformer refers to the phase difference between the primary and secondary voltages or currents. It is determined by the winding directions of the primary and secondary coils, the labeling of their start and end terminals, and the connection mode. Expressed in a clock-like format, there are 12 groups in total, numbered from 0 to 11.The DC method is commonly used to measure the transformer's connection group, mainly to verify whether the con
Vziman
07/26/2025
What is the sequence for powering down the transformer?
What is the sequence for powering down the transformer?
The sequence for shutting down a main transformer is as follows: when de-energizing, the load side should be shut down first, followed by the power supply side. For energizing operations, the reverse order applies: the power supply side is energized first, then the load side. This is because: Energizing from the power supply side to the load side makes it easier to identify the fault range and take prompt judgment and handling measures in case of a fault, preventing the fault from spreading or e
Rockwell
07/26/2025
What are the methods for switching operations of station transformers?
What are the methods for switching operations of station transformers?
Let's take an auxiliary power system with two station transformers as an example. When one station transformer needs to be out of service, there are two operation methods: non-interruptive power supply and instantaneous power interruption. Generally, the method of instantaneous power interruption on the low-voltage side is preferred.The operation method for instantaneous power interruption on the low-voltage side is as follows:Open the 380V power incoming circuit breaker of the corresponding sec
Vziman
07/26/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!