Wave Winding: Simplex, Duplex, Retrogressive And Progressive Wave Windings

Encyclopedia
08/20/2024

Wave Winding: Simplex, Duplex, Retrogressive And Progressive Wave Windings 


Key learnings:

 

Wave Winding Definition: A wave winding is defined as a type of armature winding where the end of one coil connects to the start of another, creating a wave-like pattern.

 

Simplex Wave Winding: Simplex wave winding has odd back pitch and front pitch that are nearly equal and suitable for high voltage, low current machines.

 

Duplex Wave Winding: Duplex wave winding involves two parallel paths and is used for higher current ratings.

 

Retrogressive Wave Winding: In retrogressive wave winding, after one round of the armature, the coil falls into a slot left of its starting slot.

 

Progressive Wave Winding: In progressive wave winding, after one round of the armature, the coil falls into a slot right of its starting slot.

 

What is a Wave Winding?

 

A wave winding (also known as a series winding) is defined as a type of armature winding in DC machines, alongside lap winding.

 

In a wave winding, we connect the end of one coil to the start of another coil of the same polarity. The coil side (A – B) progresses forward around the armature to another coil side and goes on successively passing through North and South poles until it returns to a conductor (A1-B1) lying under the starting pole.

 

This winding forms a wave with its coil, that’s why we call it a wave winding. Since we connect the coils in series, it is also referred to as a series winding. A diagram of a wave winding configuration is shown below.

图片6.png

Wave windings can be further classified into:

 

Simplex wave windings

Duplex wave windings

Retrogressive wave windings

Progressive wave windings

 

Progressive Wave Winding

 

If, after one round of the armature, the coil falls into a slot to the right of its starting slot, it is called progressive wave winding.

图片7.png

Retrogressive Wave Winding

 

If, after one round of the armature, the coil falls into a slot to the left of its starting slot, it is called retrogressive wave winding.

图片8.png

Here in the picture above we can see that 2nd conductor CD is in the left of the 1st conductor.

 

Important Points about Simplex Wave Winding

图片9.png

 

In simplex wave winding, the back pitch (YB) and front pitch (YF) are both odd and have the same sign.

 

The back-pitch and front-pitch are nearly equal to the pole pitch and maybe equal or differ by ±2. + for progressive winding, – for retrogressive winding.

图片10.gif

 

Here, Z is the no of conductors in the winding. P is the no of poles.

 

Average pitch (YA) must be an integer number, because it may close itself.

 

We take ± 2 (two) because after one round of the armature the winding falls sort of two conductors.

 

If we take an average pitch Z/P then after one round the winding will close itself without including all coil sides.

 

Since average pitch must be an integer, this winding is not possible with any no. of conductors.

 

Let us take 8 conductors in a 4 pole machine.

图片11.png

 

Being fractional no the wave winding is no possible but if there was 6 conductors then the winding can be done. Since,

图片12.png

 

For this problem the DUMMY COILS are introduced.

 

Dummy Coil

Wave winding is only possible with specific numbers of conductors and slot combinations. Standard stampings in the winding shop might not always match the design requirements, so dummy coils are used in such cases.

 

These dummy coils are placed in the slots to give the machine the mechanical balance but they are not electrically connected to the rest of the winding.

图片13.png

 

In multiplex wave winding:

图片14_WH_300x15px.jpg

 

Where:

 

m is the multiplicity of the winding

m = 1 for simplex winding

m = 2 for duplex winding

图片16.gif

 

Construction of Wave Windings

 

Let us develop a simplex and progressive wave winding diagram of a machine having 34 conductors in 17 slots and 4 poles.

 

Average pitch:

图片17.gif

 

Now we have to construct a table for the connection diagram:

图片18.png

 

Wave Winding Diagram

图片19.png

Simplex Wave Winding Advantages

The advantages of simplex wave windings include:

 

In this winding, only two brushes are required but more parallel brushes can be added to make it equal to the no. of poles. If one or more brushes set poor contacts with the commutator, satisfactory operation is still possible.

 

This winding gives sparkles commutation. The reason behind that it has two parallel paths irrespective of the number of poles of the machine. The conductors in each of the two parallel paths distributed around the armature in the entire circumference.

 

No. of conductors in each path = Z/2, Z is the total no. of conductors.

 

Generated emf = average emf induced in each path X Z/2

 

For a given number of poles and armature conductors, it gives more emf than that of lap winding. Hence wave winding is used in high voltage and low current machines. This winding is suitable for small generators circuit with a voltage rating of 500-600V.

 

Current flowing through each conductor.

图片20_WH_350x39px.jpg

Ia is the armature current. The current per path for this kind of winding must not be exceeded 250A.

 

The resultant emf around the entire circuit is zero.

 

Simplex Wave Winding Disdvantages

 

The disadvantages of simplex wave windings include:

 

Wave winding cannot be used in machines having higher current rating because it has only two parallel paths.


Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
For users, when purchasing a 35kV new energy transformer, choosing between dry-type, mineral oil-filled, or vegetable oil-filled types involves multiple considerations. These include user habits, maintenance-free performance, safety and fire resistance, volume and weight, among others. However, cost differences are undoubtedly one of the most crucial factors.To illustrate the issue intuitively, this paper selects a three-level energy efficiency dual-winding new energy transformer with a rated ca
Ron
07/26/2025
What is the connection group of a transformer?
What is the connection group of a transformer?
Transformer Connection GroupThe connection group of a transformer refers to the phase difference between the primary and secondary voltages or currents. It is determined by the winding directions of the primary and secondary coils, the labeling of their start and end terminals, and the connection mode. Expressed in a clock-like format, there are 12 groups in total, numbered from 0 to 11.The DC method is commonly used to measure the transformer's connection group, mainly to verify whether the con
Vziman
07/26/2025
What is the sequence for powering down the transformer?
What is the sequence for powering down the transformer?
The sequence for shutting down a main transformer is as follows: when de-energizing, the load side should be shut down first, followed by the power supply side. For energizing operations, the reverse order applies: the power supply side is energized first, then the load side. This is because: Energizing from the power supply side to the load side makes it easier to identify the fault range and take prompt judgment and handling measures in case of a fault, preventing the fault from spreading or e
Rockwell
07/26/2025
What are the methods for switching operations of station transformers?
What are the methods for switching operations of station transformers?
Let's take an auxiliary power system with two station transformers as an example. When one station transformer needs to be out of service, there are two operation methods: non-interruptive power supply and instantaneous power interruption. Generally, the method of instantaneous power interruption on the low-voltage side is preferred.The operation method for instantaneous power interruption on the low-voltage side is as follows:Open the 380V power incoming circuit breaker of the corresponding sec
Vziman
07/26/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!