Parallel Operation of Alternators

Encyclopedia
08/19/2024

Alternator Definition

An alternator is defined as an AC generator that induces EMF in a stationary wire using a rotating magnetic field, following Faraday’s law of induction.

Conditions for Parallel Operation

  • The phase sequence of the incoming machine’s voltage must match the bus bar’s voltage.

  • The RMS line voltage (terminal voltage) of the bus bar or already running machine and the incoming machine should be the same.

  • The phase angle of the two systems should be equal.

  • The frequency of the two terminal voltages (incoming machine and the bus bar) should be nearly the same. Large power transients will occur when frequencies are not nearly equal.

 Synchronizing Process

Synchronizing involves adjusting terminal voltages and checking phase sequences using a Synchroscope or three-lamp method.

Voltage and Frequency Matching

Ensure terminal voltages and frequencies are nearly identical to avoid power surges and equipment damage.

General Procedure for Paralleling Alternators

The figure below shows an alternator (generator 2) being paralleled with a running power system (generator 1). These two machines are about to synchronize for supplying power to a load. Generator 2 is about to parallel with the help of a switch, S1. This switch should never be closed without satisfying the above conditions.

9ca3324b8f5cd6d7ab25481d285249e8.jpeg

 To equalize terminal voltages, adjust the incoming machine’s terminal voltage by changing its field current. Use voltmeters to match it with the line voltage of the running system.

 There are two methods to check the phase sequence of the machines. They are as follows

  • First one is using a Synchroscope. It is not actually check the phase sequence but it is used to measure the difference in phase angles.

  • Second method is three lamp method (Figure 2). Here we can see three light bulbs are connected to the terminals of the switch, S1. Bulbs become bright if the phase difference is large. Bulbs become dim if the phase difference is small. The bulbs will show dim and bright all together if phase sequence is the same. The bulbs will get bright in progression if the phase sequence is opposite. This phase sequence can be made equal by swapping the connections on any two phases on one of the generators.

c2ba5659db6dd0fb9babf25d41bc95ac.jpeg

Next, check and verify that the frequencies of the incoming and running systems are nearly the same. This can be done by observing the dimming and brightening of the lamps.

When the frequencies are nearly equal, the two voltages (incoming alternator and running system) will alter the phase gradually. These changes can be observed and the switch, S1 can be made closed when the phase angles are equal.

Advantages of Parallel Operation

  • When there is maintenance or an inspection, one machine can be taken out from service and the other alternators can keep up for the continuity of supply.

  • Load supply can be increased.

  • During light loads, more than one alternator can be shut down while the other will operate in nearly full load.

  • High efficiency.

  • The operating cost is reduced.

  • Ensures the protection of supply and enables cost-effective generation.

  • The generation cost is reduced.

  • Breaking down of a generator does not cause any interruption in the supply.

  • Reliability of the whole power system increases.

Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
Cost Differences and Performance Comparison of 35kV New Energy Transformers Based on Dry-Type, Mineral Oil, and Vegetable Oil
For users, when purchasing a 35kV new energy transformer, choosing between dry-type, mineral oil-filled, or vegetable oil-filled types involves multiple considerations. These include user habits, maintenance-free performance, safety and fire resistance, volume and weight, among others. However, cost differences are undoubtedly one of the most crucial factors.To illustrate the issue intuitively, this paper selects a three-level energy efficiency dual-winding new energy transformer with a rated ca
Ron
07/26/2025
What is the connection group of a transformer?
What is the connection group of a transformer?
Transformer Connection GroupThe connection group of a transformer refers to the phase difference between the primary and secondary voltages or currents. It is determined by the winding directions of the primary and secondary coils, the labeling of their start and end terminals, and the connection mode. Expressed in a clock-like format, there are 12 groups in total, numbered from 0 to 11.The DC method is commonly used to measure the transformer's connection group, mainly to verify whether the con
Vziman
07/26/2025
What is the sequence for powering down the transformer?
What is the sequence for powering down the transformer?
The sequence for shutting down a main transformer is as follows: when de-energizing, the load side should be shut down first, followed by the power supply side. For energizing operations, the reverse order applies: the power supply side is energized first, then the load side. This is because: Energizing from the power supply side to the load side makes it easier to identify the fault range and take prompt judgment and handling measures in case of a fault, preventing the fault from spreading or e
Rockwell
07/26/2025
What are the methods for switching operations of station transformers?
What are the methods for switching operations of station transformers?
Let's take an auxiliary power system with two station transformers as an example. When one station transformer needs to be out of service, there are two operation methods: non-interruptive power supply and instantaneous power interruption. Generally, the method of instantaneous power interruption on the low-voltage side is preferred.The operation method for instantaneous power interruption on the low-voltage side is as follows:Open the 380V power incoming circuit breaker of the corresponding sec
Vziman
07/26/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!