• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Comprehensive Analysis of Common Accessories of Dry-Type Transformers: From Enclosures to Copper Bars, Master Key Configurations in One Article

Rockwell
Field: Manufacturing
China

Enclosures

Enclosures can be categorized into indoor and outdoor types.

For indoor applications, considering heat dissipation and maintenance needs, it is generally recommended not to install an enclosure if there is sufficient installation space. However, if required by the user, enclosures with multiple observation holes can be provided. Enclosures can also be painted in colors preferred by the user.

The protection level of enclosures is typically IP20 or IP23:

  • IP20 prevents the ingress of solid foreign objects larger than 12 mm and protects against accidental impacts.

  • In addition to the functions of IP20, IP23 can prevent water droplets from entering within a 60-degree vertical angle, making it suitable for outdoor installation.

Enclosure materials include ordinary steel plates, injection-molded plastics, stainless steel plates, aluminum alloy composite plates, etc.

Enclosures.jpg

Temperature Controllers

All transformers are equipped with overheating protection devices. These devices detect and control the transformer temperature via PT thermistors built into the low-voltage windings, and output digital signals through an RS232/485 communication interface. The device provides the following functions:

  • During transformer operation, the temperature values of the three-phase windings are displayed on the circuit.

  • Displays the temperature value of the hottest-phase winding.

  • Over-temperature alarm and over-temperature shutdown.

  • Audible and visual alarms, and fan activation.

Temperature Controllers.jpg

Air-Cooling Devices

  • The cooling methods for dry-type transformers can be divided into natural air cooling (AN) and forced air cooling (AF).

  • Under natural air cooling (AN), the transformer can continuously supply 100% of its rated capacity under normal operating conditions.

  • Under forced air cooling (AF), a 50% capacity increase can be achieved under normal operating conditions, making it suitable for various emergency overloads or intermittent overload operations. Continuous overload operation using forced air cooling (AF) is generally not recommended, as it leads to greater increases in load losses and impedance resistance.

Air-Cooling Devices.jpg

Copper Bars

  • Generally, the cable inlet/outlet methods are classified into top inlet/outlet, bottom inlet/outlet, and side inlet/outlet.

  • For transformers with a rated power ≤ 200 kVA, the conventional outlet method is still used; side outlets are connected by the user via cables.

  • When the rated power is ≥ 1600 kVA:

  • Double-row feeders with a spacing of 10 (for 1600–2000 kVA) or 12 (for 2500 kVA) are used for phases A, B, and C.

  • Since the neutral line is located at the top of the transformer, if the neutral line needs to be led out from the bottom of the switchgear, it is recommended that the transformer’s neutral line still enters the switchgear from the top.

Give a tip and encourage the author!

Recommended

Main Transformer Accidents and Light Gas Operation Issues
1. Accident Record (March 19, 2019)At 16:13 on March 19, 2019, the monitoring background reported a light gas action of No. 3 main transformer. In accordance with the Code for Operation of Power Transformers (DL/T572-2010), operation and maintenance (O&M) personnel inspected the on-site condition of No. 3 main transformer.On-site confirmation: The WBH non-electrical protection panel of No. 3 main transformer reported a Phase B light gas action of the transformer body, and the reset was ineff
02/05/2026
Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
01/29/2026
What’s the Difference Between Rectifier Transformers and Power Transformers?
What is a Rectifier Transformer?"Power conversion" is a general term encompassing rectification, inversion, and frequency conversion, with rectification being the most widely used among them. Rectifier equipment converts input AC power into DC output through rectification and filtering. A rectifier transformer serves as the power supply transformer for such rectifier equipment. In industrial applications, most DC power supplies are obtained by combining a rectifier transformer with rectifier equ
01/29/2026
How to Judge, Detect and Troubleshoot Transformer Core Faults
1. Hazards, Causes, and Types of Multi-Point Grounding Faults in Transformer Cores1.1 Hazards of Multi-Point Grounding Faults in the CoreUnder normal operation, a transformer core must be grounded at only one point. During operation, alternating magnetic fields surround the windings. Due to electromagnetic induction, parasitic capacitances exist between the high-voltage and low-voltage windings, between the low-voltage winding and the core, and between the core and the tank. The energized windin
01/27/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.